AT y S S / S d
Переключатель с электроприводом
Руководство
RU
СОДЕРЖАНИЕ
1. ОБЩИЕ ИНСТРУКЦИИ ПО ТЕХНИКЕ БЕЗОПАСНОСТИ
. . . . . . . . . . . . . . . . . . . . . . . .4
2. ВВЕДЕНИЕ
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
3. АССОРТИМЕНТ ИЗДЕЛИЙ СЕРИИ AT
Y
S
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
3.1. КЛЮЧЕВЫЕ ХАРАКТЕРИСТИКИ СЕРИИ AT
Y
S «ВПЛОТНУЮ ДРУГ К ДРУГУ»
. . . . . . . . . .6
4. БЫСТРЫЙ ЗАПУСК
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
5. ОБЗОР
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
5.1. AT
Y
S
S
И AT
Y
S
S
D: ЗНАКОМСТВО С ИЗДЕЛИЕМ RTSE
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
5.2. AT
Y
S : ИДЕНТИФИКАЦИЯ ИЗДЕЛИЯ RTSE
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
5.3. AT
Y
S
S
И AT
Y
S
S
D : СВЕДЕНИЯ ОБ ОКРУЖАЮЩЕЙ СРЕДЕ RTSE
. . . . . . . . . . . . . . . . . . . .12
5.3.1. КЛАСС ЗАЩИТЫ IP
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
5.3.2. УСЛОВИЯ РАБОТЫ
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
5.3.2.1. ТЕМПЕРАТУРА/НОМИНАЛЬНЫЙ ТОК
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
5.3.2.2. ОГРАНИЧЕНИЕ ТЕМПЕРАТУРЫ/УПРАВЛЯЮЩЕГО НАПРЯЖЕНИЯ
. . . . . . . . . . . . . . . . . .12
5.3.2.3. ГИГРОМЕТРИЯ
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
5.3.2.4. ВЫСОТА НАД УРОВНЕМ МОРЯ
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
5.3.3. УСЛОВИЯ ХРАНЕНИЯ
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
5.3.3.1. ТЕМПЕРАТУРА
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
5.3.3.2. СРОК ХРАНЕНИЯ
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
5.3.3.3. ПОЛОЖЕНИЕ ПРИ ХРАНЕНИИ
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
5.3.4. ЕМКОСТЬ И ВЕС ПРИ ТРАНСПОРТИРОВКЕ
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
5.3.5. ЗНАК СООТВЕТСТВИЯ ТРЕБОВАНИЯМ ЕВРОПЕЙСКОГО СОЮЗА ПО
БЕЗОПАСНОСТИ ПРОДУКЦИИ
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
5.3.6. ОБРАБОТКА БЕЗ СВИНЦА
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
5.3.7. WEEE
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
5.3.8. ЭЛЕКТРОМАГНИТНАЯ СОВМЕСТИМОСТЬ
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
6. УСТАНОВКА
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
6.1. AT
Y
S
S
И AT
Y
S
S
D: РАЗМЕРЫ ИЗДЕЛИЯ RTSE
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
6.2. AT
Y
S : ОРИЕНТАЦИЯ ПРИ УСТАНОВКЕ RTSE
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
6.3. AT
Y
S : СБОРКА УСТАНОВЛЕННЫХ ЗАКАЗЧИКОМ АКСЕССУАРОВ RTSE
. . . . . . . . . . . . . .16
6.3.1. УСТАНОВКА СОЕДИНИТЕЛЬНОЙ ШИНЫ
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
6.3.2. КЛЕММНЫЕ КРЫШКИ
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
6.3.2.1. КРЫШКИ ИСХОДЯЩИХ КЛЕММ (ПРИ ИСПОЛЬЗОВАНИИ СОЕДИНИТЕЛЬНЫХ ШИН)
.17
6.3.2.2. КРЫШКИ ВХОДЯЩИХ КЛЕММ
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
6.3.2.3. УПЛОТНИТЕЛЬНОЕ УСТРОЙСТВО ДЛЯ ПОВЫШЕНИЯ БЕЗОПАСНОСТИ
. . . . . . . . . . . .18
6.3.3. РУКОЯТКА НЕПОСРЕДСТВЕННОГО УПРАВЛЕНИЯ И ЗАЖИМ НАКОПИТЕЛЯ
. . . . .19
7. РАЗЪЕМЫ
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
7.1. СИЛОВЫЕ КОНТУРЫ
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
2
ATyS S/Sd
— См.: 541 892 C
ATyS S/Sd
7.1.1. КАБЕЛЬНЫЕ СОЕДИНЕНИЯ
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
7.1.2. КЛЕММЫ ДЛЯ ПОДАЧИ ПИТАНИЯ
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
7.1.3. ПЛОЩАДЬ ПОПЕРЕЧНОГО СЕЧЕНИЯ СИЛОВОГО КАБЕЛЯ
. . . . . . . . . . . . . . . . . . . . .20
7.2. КОНТУРЫ УПРАВЛЕНИЯ
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
7.2.1. ТИПИЧНЫЕ МОНТАЖНЫЕ СХЕМЫ AT Y S S И AT Y S S D
. . . . . . . . . . . . . . . . . . . . . . . . . . .21
7.2.1.1. AT Y S S D: 230 В ПЕР. ТОКА X 2 (СДВОЕННЫЙ ИСТОЧНИК ПИТАНИЯ )
. . . . . . . . . . . . . . .21
7.2.1.2. AT Y S S : 230 В ПЕР. ТОКА
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
7.2.1.3. AT Y S S : 12 В ПОСТ. ТОКА
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
7.2.1.4. AT Y S S : 24/48 В ПОСТ. ТОКА
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
7.2.1.5. ВНЕШНИЙ ИСТОЧНИК ПИТАНИЯ (400 В ПЕР. ТОКА)
. . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
7.2.2. AT Y S S RTSE + КОНТРОЛЛЕРЫ ATS ТИПА AT Y S C30 И AT Y S C40
. . . . . . . . . . . . . . . . .23
7.2.3. ВХОДНЫЕ И ВЫХОДНЫЕ КОНТАКТЫ AT Y S S И AT Y S S D
. . . . . . . . . . . . . . . . . . . . . . . .24
7.2.4. НАИМЕНОВАНИЕ, ОПИСАНИЕ И ХАРАКТЕРИСТИКИ КЛЕММЫ.
. . . . . . . . . . . . . . . . . .24
8. РЕЖИМЫ РАБОТЫ AT
Y
S
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
8.1. АВТОМАТИЧЕСКИЙ РЕЖИМ: РАБОТА ПРИ ПОДАЧЕ ЭЛЕКТРОПИТАНИЯ
. . . . . . . . . . . . .26
8.1.1. ИСТОЧНИК ПИТАНИЯ
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
8.1.2. ВВОД КОМАНД — ОПИСАНИЕ
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
8.1.3. ВВОД КОМАНД — ТЕХНИЧЕСКИЕ ДАННЫЕ
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
8.1.4. ВВОД КОМАНД — УПРАВЛЯЮЩАЯ ЛОГИКА
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
8.1.5. ВЫХОДЫ СУХОГО КОНТАКТА — ДОПОЛНИТЕЛЬНЫЕ
. . . . . . . . . . . . . . . . . . . . . . . . . .27
8.2. РУЧНОЕ УПРАВЛЕНИЕ
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28
8.3. БЛОКИРОВКА
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28
9. ХАРАКТЕРИСТИКИ AT
Y
S
S . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
10. РУКОВОДСТВО ПО ПОИСКУ И УСТРАНЕНИЮ НЕИСПРАВНОСТЕЙ
. . . . . . . . .30
11. ЗАПАСНЫЕ ЧАСТИ И АКСЕССУАРЫ
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
11.1. АКСЕССУАРЫ
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
11.2. ЗАПАСНЫЕ ЧАСТИ AT
Y
S
S
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
11.2.1. МОДУЛЬ ЭЛЕКТРОПРИВОДА
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
11.2.3. ЗАПАСНЫЕ ПЕРЕКЛЮЧАТЕЛИ ПИТАНИЯ: AT Y S S И AT Y S S D
. . . . . . . . . . . . . . . . . . .32
11.2.4. РУКОЯТКА НЕПОСРЕДСТВЕННОГО РУЧНОГО УПРАВЛЕНИЯ В
АВАРИЙНОМ РЕЖИМЕ
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
11.2.5. МОНТАЖНЫЕ НОЖКИ
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
11.2.6. НАБОР КОНЦЕВЫХ РАЗЪЕМОВ
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .33
12. ИНФОРМАЦИЯ О ЗАКАЗЕ AT
Y
S
S
И AT
Y
S
S
D
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .33
12.1. РЕГИСТРАЦИОННЫЕ НОМЕРА КАТАЛОГА AT
Y
S
S
И AT
Y
S
S
D
. . . . . . . . . . . . . . . . . . . . . . .33
ATyS S/Sd
— См.: 541 892 C 3
1. ОБЩИЕ ИНСТРУКЦИИ ПО ТЕХНИКЕ
БЕЗОПАСНОСТИ
š
В данном руководстве содержатся инструкции по технике безопасности, подключению и эксплуатации автоматических переключателей AT y S S и AT y S S d производства компании SOCOMEC.
š
Независимо от того, в каком виде продаются AT y S S и AT y S S d — как отдельное изделие, запасная часть, комплексное решение или часть другой конфигурации — эти устройства всегда должны устанавливаться и вводиться в эксплуатацию квалифицированным, опытном персоналом в соответствии с рекомендациями производителя, с учетом инженерно-технической практики и после изучения новейшего выпуска соответствующего руководства к изделию.
š
Эксплуатация изделия и другого связанного с ним оборудования, включая операции по техническому обслуживанию, должна выполняться соответствующим образом обученным, квалифицированным персоналом.
š
Каждое изделие поставляется с ярлыком или маркировкой другого типа, где указано номинальное значение и другая важная информация, относящаяся к изделию. Кроме того, следует обращать внимание на маркировку и учитывать значения и ограничения, касающиеся конкретного изделия, перед его установкой и вводом в эксплуатацию.
š Использование изделия не по назначению, не в соответствии с рекомендациями компании
SOCOMEC или без учета указанных параметров и ограничений может привести к телесным повреждениям и/или повреждению оборудования.
š Доступ к данному руководству должен предоставляться всем, кому необходимо его прочитать для использования AT y S S и AT y S S d.
š
Каждое изделие AT y S S и AT y S S d соответствует Европейским директивам, определяющим использование данного типа изделия, и содержит знак соответствия требованиям Европейского союза по безопасности продукции.
š
Запрещается открывать кожух AT y S S (под напряжением или без напряжения), поскольку внутри изделия может быть опасное напряжение, подаваемое, например, от внешних контуров.
š Не держать в руках кабели управления или питания, подключенные к AT y S, если они находятся под напряжением или подключены к сети напрямую или косвенно.
š Напряжение, под которым находится данное изделие, может привести к телесным повреждениям, поражению электрическим током, ожогам или смерти. Перед выполнением технического обслуживания токоведущих частей или других частей поблизости от оголенных токоведущих частей и других работ с ними убедитесь в том, что переключатель, а также все контуры управления и связанные с ними контуры обесточены.
ОПАСНО ПРЕДУПРЕЖДЕНИЕ ВНИМАНИЕ
РИСК :
Поражение электрическим током, ожоги, смерть
РИСК:
Возможны телесные повреждения
РИСК:
Повреждение оборудования
š
Как минимум, AT y S S и AT y S S d соответствуют следующим международным стандартам:
— IEC 60947-6-1
— GB 14048-11
— EN 60947-6-1
— IEC 60947-3
— IS 13947-3
— EN 60947-3
— BS EN 60947-6-1 — NBN EN 60947-3
— NBN EN 60947-6-1 — BS EN 60947-3
Информация, содержащаяся в данном руководстве, подлежит изменению без предварительного уведомления, предназначена только для общего ознакомления и не подразумевает договорных обязательств.
4
ATyS S/Sd
— См.: 541 892 C
ATyS S/Sd
2. ВВЕДЕНИЕ
Серия «коммутационного оборудования с дистанционным управлением» (RTSE) AT y S S предназначена для использования в системах электропитания для безопасного переключения подачи нагрузки от нормального и альтернативного источника. Переключение производится с разрывом цепи и с минимальным прерыванием подачи питания во время переключения в полном соответствии со стандартами IEC 60947-6-1, GB 14048-11 и другими международными стандартами TSE согласно списку.
AT y S S и AT y S S d — коммутационное оборудование (переключатели) для переключения полной нагрузки, основными компонентами которого являются устройства, созданные с использованием признанных технологий и соответствующие требованиям стандартов IEC 60947-3.
Изделия AT y S S и AT y S S d, относящиеся к классу PC RTSE и способные «производить и выдерживать токи короткого замыкания», соответствуют требованиям стандарта IEC 60947-3 к категориям применения до
AC23B, GB 14048-11, IEC 60947-6-1 и требованиям эквивалентных стандартов к категориям применения до
AC32B.
Автоматические переключатели источника AT y S S и AT y S S d соответствуют следующим положениям.
š
Управление электропитанием и безопасностью нормального и альтернативного источника.
š
Законченное изделие, поставляемое в виде полностью собранного и протестированного решения.
š Интуитивно понятный человеко-машинный интерфейс для использования в случае аварии/работы на месте.
š
Надежный встроенный выключатель.
š Ясное указание на положение переключателя.
š Надежная встроенная механическая блокировка.
š
Стабильные положения (I – 0 – II), на которые не влияет вибрация и ударная нагрузка.
š
Постоянное давление на контактах, на которое не влияет напряжение сети.
š Низкое энергопотребление и фактически отсутствие потребления в нормальном, альтернативном или выключенном положении.
š
Быстрый, легкий и безопасный переход в ручной режим работы под нагрузкой в случае аварии.
(Ручной режим действует как при использовании электропривода, так и без него.)
š
Прочность, отсутствие ошибок и блокировка навесным замком.
š Простота установки и эргономичность.
š Минимальное время простоев благодаря простоте технического обслуживания.
š
Интерфейс для простого и безопасного управления электроприводом.
š
Встроенные и независимые дополнительные контакты положения переключателя.
š Достаточное количество аксессуаров для удовлетворения особых требований.
š Совместимость практически с любой моделью контроллера ATS, AMF, Genset.
(Обычно используется контроллер AT y S C 30/ C 40 ATS или подобная модель, а управление производится через контакты, на которых нет напряжения.)
š Непрерывная подача электропитания при выполнении большинства задач…
Сеть/сеть Сеть/ Genset Genset/ Genset
ATyS C30 ATyS D20 ATyS C40
ATyS C30 ATyS D10
ATyS Sd
ATyS S
ATyS S
ATyS S/Sd
— См.: 541 892 C 5
3. АССОРТИМЕНТ ИЗДЕЛИЙ СЕРИИ AT
y
S
Серия AT y S спроектирована во взаимодействии с центром обеспечения качества SOCOMEC во
Франции, который гордится своей собственной испытательной лабораторией электропитания 100MVA, аккредитованной COFRAC и сотрудничающей с такими организациями, как KEMA, CEBEC, UL, CSA, ASTA,
«Регистр Ллойда», Bureau Véritas, BBJ-SEP, EZU, GOST-R и другими.
SOCOMEC производит продукцию по управлению электропитанием и для обеспечения безопасности с
1922 года. Первое поколение автоматических переключателей SOCOMEC было представлено в 1990 году, и сегодня торговая марка AT y S признана большинством игроков на рынке товаров для электроэнергетики.
Серия AT y S включает в себя полный набор коммутационного оборудования с дистанционным управлением
(RTSE), а также автоматические, полностью интегрированные изделия и решения (ATSE). Выбор подходящего изделия AT y S зависит от области применения, а также особенностей оборудования, на котором устанавливается изделие AT y S.
Данное руководство содержит подробные сведения и инструкции, касающиеся только RTSE “AT y S S и AT y S
S d”. Для получения информации обо всех остальных изделиях серии AT y S обращайтесь к соответствующему руководству по конкретному изделию. (Доступны для загрузки на веб-сайте www.socomec.com
).
Обзор всего набора AT y S представлен ниже.
(AT y S S и AT y S S d — коммутационное оборудование, подробно описанное в настоящем руководстве.)
Подходящее изделие ATyS для конкретной сферы применения…
AT
y
S: небольшая площадь основания
AT
y
S
M
: модульный профиль
Конфигурация «вплотную друг к другу»
ATyS Sd
Small Genset с DPS
AT
y
S
S (RTSE)
Small Genset
AT
y
S p
Управление питанием
/ Genset
AT
y
S g
Простое управление
Genset
AT
y
S
RTSE
AT
y
S t
Управление трансформатором
AT
y
S d
Двойное энергоснабжение (DPS)
AT
y
S
M
6e
Улучшенное управление Genset
AT
y
S
M
6s
Простое управление
Genset
AT
y
S
M
6b
Управление трансформатором (в здании)
AT
y
S
M
3s
RTSE
Конфигурация «вплотную друг к другу»
3.1. Ключевые характеристики серии AT
y
S «вплотную друг к другу»
Выбор подходящего изделия AT y S зависит от области применения, требуемых функциональных возможностей, а также особенностей оборудования, на котором устанавливается изделие AT y S. Ниже приводится схема выбора изделий, содержащая ключевые характеристики каждого изделия (конфигурация
«вплотную друг к другу»), позволяющая быстро разобраться в продукции и выбрать подходящее изделие
AT y S для удовлетворения конкретных нужд.
6
ATyS S/Sd
— См.: 541 892 C
ATyS S/Sd
AT y S S AT y S S d AT y S AT y S d AT y S t AT y S g AT y S p
Автоматическое переключение управления через изолированные контакты
Ручное управление в аварийном режиме работы с помощью выносной рукоятки
Широкополосная подача управляющего напряжения переменного тока
Широкополосная подача управляющего напряжения постоянного тока
Реле сторожевого таймера для обеспечения доступности изделия
Номинальный ток 40–125 A в соответствии с индикацией или ş$ɀɇɛš
Блок управления ручной коррекций и принудительное переключение в нулевое положение (выкл)
Интегрированные дополнительные контакты положения (I –
O – II)
Светодиодный индикатор доступности источника
Подключение модуля дистанционного дисплея RJ45 для
AT y S D10
Интегрированная двойная подача питания
Сеть — сетевые приложения
Сеть — приложения Genset
Genset — приложения Genset
Предварительно заданный фиксированный ввод/вывод
Программируемый ввод/вывод
Дополнительные программируемые модули ввода/вывода
(дополнительно до 4 модулей)
Коммутационное оборудование с дистанционным управлением (RTSE класса PC)
Автоматическое коммутационное оборудование (ATSE класса PC)
Дистанционное + ручное управление
Автоматическое + дистанционное + ручное управление
Автоматическое + дистанционное + местное + ручное управление
Автоматическая настройка уровня напряжения и частоты
Светодиодный индикатор положения переключателя
Уплотнительная крышка для обеспечения безопасности
Настройка с помощью потенциометров и DIPпереключателей
Испытание под нагрузкой
Испытание не под нагрузкой
Программируемая конфигурация с использованием клавишной панели и жидкокристаллического дисплея
Измерения: кВт; кВАр; кВА + кВт/ч; кВАр·ч; кВА·ч
Связь по протоколу RS485 + Ethernet + шлюз Ethernet
(дополнительно)
Доступ к веб-серверу через дополнительный модуль Ethernet
(дополнительно)
Программное обеспечение, обеспечивающее легкую настройку (через Ethernet/Modbus)
Подключение дистанционного терминала RJ45 для AT y S D20
Регистратор данных для записи событий с помощью RTC
(через Ethernet/Modbus)
Функциональные возможности программируемого пульта управления двигателя (через Ethernet/Modbus)
Многоуровневый доступ путем ввода пароля
Функция сброса нагрузки
Функциональные возможности управления энергоресурсами
Функциональные возможности ограничения пиковой нагрузки
Модуль связи 4–20 мА (дополнительно)
Модуль пульсирующего выходного напряжения, кВт/ч
(дополнительно)
Счетчики кВт/ч, перестановка…
Жидкокристаллический дисплей для программирования, выполнения измерений, таймеров и счетчиков
Возможность добавления дополнительной функциональности
š
š
š
š
š
š
š
40–125
A
40–125
A
š
š
š
š
š
š
š
š
š
š
š
š
š
š
š
š
š
š
š
š
š
š
š
š
š
š
š
š
š
š
š
š
š
š
š
š
š
š
š š š š š
š š š š š
š
š
š
š
š
š
š
š
š
š
š
š
š
š
š
AT y S D20
š š
š
š
š š
š
5/1
š
5/1
š
9/2
š
11/3
š
5/2
š
6/1
š
8/8
š š
š š š
š š
š š
š
š
š
š
š
š
š
š
š
š
š
š
š
š
š
š
š
š
š
š
š
š
š
š
š
š
š
š
š
š
š
š
ATyS S/Sd
— См.: 541 892 C 7
4. БЫСТРЫЙ ЗАПУСК
541 891 D – 08/13 – RU
Недоговорной документ.
без предварительного уведомления.
Монтаж и пусконаладка
RU
БЫСТРЫЙ ЗАПУСК
AT y S S / S d
Моторизованный переключатель
Перед первым использованием
Проверить следующее при получении устройства и после удаления упаковки:
■
Упаковка и содержимое в надлежащем состоянии.
■
Артикул устройства соответствует номеру, указанному в заказе.
■
В комплект должны входить:
ATyS S/Sd — 1 шт.; рукоятка и зажим для хранения — 1 шт.; инструкция по быстрому запуску; набор, включающий 3 клеммных зажима — 1 шт.;
набор, включающий 16 винтов, гаек и шайб для подключения силовой секции — 1 шт.;
Внимание!
Риск поражения электрическим током, получения ожогов или причинения вреда здоровью персонала и/или повреждения оборудования.
Инструкция по быстрому запуску предназначена для уже прошедшего необходимое обучение персонала по монтажу и пусконаладке устройства. Более подробные сведения см. в руководстве по эксплуатации устройства, доступном на веб-сайте SOCOMEC.
■
Данное устройство должно быть установлено и запущено в эксплуатацию квалифицированным персоналом, имеющим допуск.
■
Техническое обслуживание и прочие сервисные работы должны выполняться обученным персоналом, допущенным к выполнению данных работ.
■
Не держать в руках кабели и прочие соединения, если они находятся под напряжением или подключены к сети напрямую или косвенно.
■
Всегда использовать прибор индикации для проверки отсутствия напряжения.
■
Необходимо убедиться, что металлические предметы не упали в электротехнический шкаф (риск образования электрической дуги).
Отсутствие необходимой инженерно-технической практики, а также несоблюдение данных требований техники безопасности, может привести к травмированию пользователей или смертельному исходу.
Риск повреждения устройства
■
В случае падения или повреждения устройства иным образом, рекомендуется полностью заменить его.
Аксессуары
■
Соединительные шины 4 фазы 125 A.
■
Трансформатор управляющего напряжения 400 В ->
230 В.
■
Клеммы сторона подачи/сторона нагрузки.
■
Кронштейн разъема безопасности.
■
Переключатели напряжения.
■
4-модульная DIN-рейка.
■
Контроллер ATS типа ATyS C30 + D10/D20.
■
Контроллер ATS типа ATyS C40.
Более подробную информацию см. в руководстве пользователя к данному изделию в главе «Запасные части и аксессуары» www.socomec.com
Для загрузки брошюр, каталогов и технических руководств:
ШАГ 1
Шкаф/установка задней панели
ШАГ 2
Подключение к разъему POWER
ШАГ 3
Клеммные соединения
COMMAND/
CONTROL
ШАГ 4
Клеммные соединения подвода питания
ШАГ 5
Монтаж аварийной рукоятки
ШАГ 7B
Ручное управление
I
NOK ПРОЙДЕН
I
NOK
I
ШАГ 7C
Блокировка (в положении 0)
ШАГ 4
Ø
3x
4–8 мм
ШАГ 6
Проверка
ШАГ 7A
Автоматический режим работы (AUT)
ШАГ 7B
Ручное управление
ШАГ 7C
Блокировка
ШАГ 3
ШАГ 6
Проверка
проверить проводку и, в случае если она в норме, включить устройство.
ШАГ 7A
Автоматический режим работы
вставлена в устройство и поверните переключатель выбора режима в положение AUT.
___________________________________________________________
Логическая схема импульса
Логическая схема контактора команда I команда 0 команда II положение I положение 0 положение II
Импульс ≥ 60 мс удерживается
Замкните контакт, соответствующий необходимому положению.
Приоритет команды: I и II имеют равный приоритет над 0. Если I и II замыкаются одновременно, положение устройства не изменится.
8
ATyS S/Sd
— См.: 541 892 C
ATyS S/Sd
ШАГ 1
Установка
твердую поверхность.
Расположение:
Рекомендуется
40–125 A
Ok Ok
Точное место крепления: 0° – 45° – 90°
Все размеры указаны в мм.
104.5
11
26.5
27.5
26.5
8
37
15
Ø 6.4
115.2
198
74
14
M6
44
100
181
Вырез дверцы для монтажа передней панели (7 модулей):
125
42.5
ШАГ 2
Клеммные соединения подвода питания
Для подключения при помощи кабельных наконечников, твердых или гибких шин.
80 A 100 A 125 A 40 A 63 A
Минимальное сечение кабеля Cu (мм 2 )
Максимальное сечение кабеля Cu (мм 2 )
Тип винта
Рекомендуемый момент затяжки (Н·м)
Максимальный момент затяжки (Н·м)
10
70
M6
4,5
5,4
Все значения являются приблизительными.
16
70
M6
4,5
5,4
25
70
M6
4,5
5,4
35
70
M6
4,5
5,4
50
70
M6
4,5
5,4
1
ШАГ 3
К
C
Клеммы CONTROL/
COMMAND
Убедившись, что устройство находится в ручном режиме, подключить его с помощью поставляемых в комплекте соединителей и соответствующих проводов с поперечным сечением 1,5–2,5 мм 2 .
1
Предохр.
4 A
Тип gG
ШАГ 5
Б р размещения тки
1
2
Момент
ATyS Sd: 2 x 230 В AC
ШАГ 4
2
Предохр.
4 A
Тип gG
*Момент затяжки
317316315 314 04 03 24 23 14 13
O I II
КОНТРОЛЬ ВСПОМ. КОНТАКТЫ
ATyS S 230 В AC
1
2
Предохр.
4 A
Тип gG
317316315 314 04 03 24 23 14 13
O I II
КОНТРОЛЬ ВСПОМ. КОНТАКТЫ
ATyS S DC-исполнение: 12 В DC/24–48 В DC
1
2
*Момент
317316315 314 04 03 24 23 14 13
O I II
КОНТРОЛЬ ВСПОМ. КОНТАКТЫ
Предохр.
4 A
Тип gG
Момент затяжки винта
M3: мин.: 0,5 Н·м
22
ATyS S/Sd
— См.: 541 892 C 9
5. ОБЗОР
5.1. AT
y
S
S
и AT
y
S
S
d: Знакомство с изделием RTSE
f e
11 d
10 c b
Включено в стандартную комплектацию:
1. Положение дополнительных выходных контактов x 3
(расположение выводов индикации I – O – II: разъем с 6 контактами).
2. Входные контакты для управления/команд x 3
(расположение I – O – II : разъем с 4 контактами).
3. Окно индикации расположения переключателя I – 0 – II
I (Вкл) – O (Выкл) – II (Вкл).
4. Корпус модуля электропривода и устройство управления.
5. Рукоятка для ручного управления в аварийном режиме и зажим накопителя.
6. Местоположение вала ручного управления в аварийном режиме
(доступен только в ручном режиме).
7. Дополнительный источник питания (внимание: на рисунке показано изделие AT y S S d)
AT y S S d : 230 В пер. тока x 2 (двойная подача);
AT y S S : 230 В пер. тока, 12 В пост. тока, 24/48 В пост. тока.
8. Переключатель выбора режима: автоматический/ручной/с навесным замком.
9. Средство для запирания в положении «0». (3 x 4–8 мм).
10. Отсек питания. Узел переключателя 4P.
Содержит собственный механический фиксатор.
Задний переключатель II, передний переключатель I.
11. Стопорные выступы для монтирования задней панели AT y S x 4.
10
ATyS S/Sd
— См.: 541 892 C
Поставляется как аксессуар: a. Скоба для легкой защиты коннектора b. Клеммные крышки на стороне подачи c. Комплект для отвода напряжения d. Монтажные отверстия для аксессуара
AT y S S для DIN-рейки. (Рассчитано на
4 модуля) e. Переворачиваемые соединительные шины f. Клеммные крышки на стороне нагрузки
5
6
7
3
4
1
2 a
8
9
ATyS S/Sd
5.2. AT
y
S : Идентификация изделия RTSE
1 2
ATyS s alim 2 sources 230Vac
3
XXXXXXXX
12 11 10
1. Идентификационные ярлыки переключателя 1 (спереди) и переключателя 2 (сзади) (верх и низ).
2. Идентификационный ярлык выходных контактов.
3. Идентификационный ярлык входных контактов.
4. Идентификационный ярлык главного переключателя, содержащий электрические характеристики и применимые стандарты.
5. Тип изделия AT y S (AT y S S или AT y S S d).
6. Номинальный ток и регистрационный номер изделия AT y S S / AT y S S d.
7. Пиктограмма типа изделия (RTSE – автоматический переключатель).
8. Сведения о входящей и исходящей проводке клемм питания.
9. Полный серийный номер изделия AT y S, штрихкод и знак соответствия требованиям Европейского союза по безопасности продукции.
10. Контакты дополнительного электропитания и идентификационный ярлык.
11. Пиктограмма положения переключателя и механического фиксатора.
12. Направление вращения для ручного управления в аварийном режиме.
4
8
9
5
6
7
ATyS S/Sd
— См.: 541 892 C 11
5.3. AT
y
S
S
и AT
y
S
S
d : Сведения об окружающей среде RTSE
Изделия AT y S S и AT y S S d соответствуют следующим минимальным требованиям к условиям окружающей среды.
ø 1 mm
5.3.1. Класс защиты IP
š
IP2X от непосредственного контакта для устройства управления с электроприводом.
š
IP2X от непосредственного контакта для отсека электропитания с установленными соединениями и при подходящих, правильно установленных входных и выходных клеммных крышках.
š IP 0 для отсека с неизолированным источником питания без установленных клеммных крышек.
5.3.2. Условия работы
5.3.2.1. Температура/номинальный ток
š От -20 до +40 °C без ограничения рабочих характеристик
š От -20 до +70 °C при применении поправочного коэффициента для ограничения рабочих характеристик Kt
Kt: поправочный коэффициент
Температура
0,9
0,8 от 40 °C до 50 °C от 50 °C дo 60 °C
0,7 от 60 °C дo 70 °C
* Упрощенный метод ограничения рабочих характеристик: Ithu ≤ Ith x Kf
* Более точный расчет можно произвести для конкретных областей применения. Если это необходимо, обращайтесь в компанию SOCOMEC.
5.3.2.2. Ограничение температуры/управляющего напряжения
Температура
Окружающая среда
-20 °C
-10 °C
55 °C
70 °C
Напряжение
(переменный ток)
154–310 В
165–310 В
165–310 В
154–290 В
154–285 В
12 В постоянного тока
8,4–15,6 В
9–15,6 В
9–15,6 В
8,4–15 В
8,4–15 В
24/48 В постоянного тока
16,8–62,4 В
17,5–62,4 В
17,5–62,4 В
16,8–60 В
16,8–60 В
5.3.2.3. Гигрометрия
š влажность 80 % без конденсации при температуре 55°C;
š влажность 95 % без конденсации при температуре 40°C.
5.3.2.4. Высота над уровнем моря
š До 2000 м без ограничения рабочих характеристик.
š Для большей высоты применяются поправочные коэффициенты Ka, приведенные ниже.
Ka: поправочный коэффициент
Ue
Ie
2000 м < A ≤ 3000 м
0,95
0,85
3000 м < A ≤ 4000 м
0,8
0,85
12
ATyS S/Sd
— См.: 541 892 C
5.3.3. Условия хранения
5.3.3.1. Температура
š
От -40 до +70 °C
5.3.3.2. Срок хранения
š
Максимальный срок хранения — 12 месяцев.
š
(Рекомендация: хранить в сухом месте, исключающем коррозию и попадание соли)
5.3.3.3. Положение при хранении
ATyS S/Sd
Вертикально можно складывать максимум 4 коробки
5.3.4. Емкость и вес при транспортировке
Номинальный ток
40 A
63 A
80 A
100 A
125 A
Масса нетто
Масса брутто
AT
y
S
S
12 В пост. тока
9505 4004
9505 4006
9505 4008
9505 4010
9505 4012
3,1 кг
3,7 кг
AT
y
S
S
24/48 В пост. тока
9506 4004
9506 4006
9506 4008
9506 4010
9506 4012
3,1 кг
3,7 кг
AT
y
S
S
230 В пер. тока
9503 4004
9503 4006
9503 4008
9503 4010
9503 4012
3,15 кг
3,85 кг
AT
y
S
S
d
230 В пер. тока x2
9513 4004
9513 4006
9513 4008
9513 4010
9513 4012
3,2 кг
3,9 кг
5.3.5. Знак соответствия требованиям Европейского союза по безопасности продукции
AT y S S и AT y S S d соответствуют Европейской директиве:
š
Электромагнитная совместимость № 2004/108/CE от 15 декабря 2004 г.
š
Директива по низкому напряжению № 2006/95/CE от 12 декабря 2006 г.
5.3.6. Обработка без свинца
š AT y S S и AT y S S d соответствуют Европейская директиве по RoHS.
ATyS S/Sd
— См.: 541 892 C 13
5.3.7. WEEE
AT y S S и AT y S S d сконструированы в соответствии с директивой 2002/96/CE:
5.3.8. Электромагнитная совместимость
AT y S S и AT y S S d сконструированы в соответствии со стандартами IEC 60947-1.
Продукция класса B:
Продукция, предназначенная для установки в промышленных, торговых и жилых помещениях.
Кратковременная неустойчивость в электропитании/разрыв
(EFT/испытание на разрыв)
12 В пост. тока, вариант 2 кВ, критерии: B
24/48 В пост. тока, вариант 2 кВ, критерии: B
240 В пер. тока, вариант 2 кВ, критерии: B применимо к управляющему разъему от земли, 1 кВ
Испытание импульсными перенапряжениями
12 В пост. тока, вариант 2 кВ, критерии: B
24/48 В пост. тока, вариант 2 кВ, критерии: B
240 В пер. тока, вариант 2 кВ, критерии: B
Импульсное испытание 4,8 кВ 1,2/50us – 0,5 J – IEC 60947-1, критерии A
Электростатический разряд
(ESD)
Вариант пост. тока 4/8 кВ, критерии: B
240 В пер. тока, вариант 4/8 кВ, критерии: B
Контактный разряд 4 кВ, разряд через воздушный зазор: 8 кВ
Испытание радиочастотного излучения электромагнитных полей
Частотный диапазон: 80–1000 МГц
Вариант пост. тока 12 В — 10 В/м, критерии: A
Вариант пост. тока 24/48 В — 10 В/м, критерии: A
Вариант пер. тока 240 В — 10 В/м, критерии: А
Кондуктивные помехи, наведенные радиочастотными полями
Частотный диапазон: 0,15–80 МГц
Вариант пост. тока 12 В — 10 В, критерии: A
Вариант пост. тока 24/48 В — 10 В, критерии: A
Вариант пер. тока 240 В — 10 В, критерии: А
Испытание кондуктивного излучения
От 150 кГц до 30 МГц, класс B
Испытание излучения От 30 МГц до 1000 МГц, класс B
14
ATyS S/Sd
— См.: 541 892 C
ATyS S/Sd
6. УСТАНОВКА
6.1. AT
y
S
S
и AT
y
S
S
d: Размеры изделия RTSE
Размеры от 40 до 125 A
Все размеры указаны в мм.
104.5
11
26.5
27.5
26.5
8
37
15
Ø 6.4
115.2
198
74
14
M6
44
100
181
Вырез дверцы для монтажа передней панели (7 модулей):
125
42.5
ВНИМАНИЕ
Запланировать пространство, требуемое для установки (хранения) рукоятки для ручного управления, а также проводки.
6.2. AT
y
S : Ориентация при установке RTSE
d S S y AT
ATyS s alim 2 sources 230Vac
XXXXXXXX
XXXXXXXX
ATyS s alim 2 sources 230Vac
AUT
Ø 4 … 8mm
Ø 4 … 8mm
AUT
AT S
Не пройден
От 40 до 125 A Рекомендуется
Пройден Пройден
ВНИМАНИЕ
Всегда устанавливайте изделие на ровной и жесткой поверхности.
ATyS S/Sd
— См.: 541 892 C 15
6.3. AT
y
S : Сборка установленных заказчиком аксессуаров RTSE
ОПАСНО
Никогда не трогайте установленные заказчиком аксессуары, поскольку существует риск наличия или появления напряжения.
6.3.1. Установка соединительной шины
Весь номинальный ток: от 40 до 125 A
Соединительные шины поставляются в сборке (медные полосы 4P с номинальным током 125 A Ith) вместе с соответствующими болтами, гайками и шайбами. Для упрощения установки на клеммах AT y S S закреплять соединительные шины рекомендуется перед закреплением устройства на опорной пластине.
Сначала рекомендуется установить шину рядом с модулем электропривода, а затем соседнюю шину, пока не будут установлены все 4 полюса. Обратите внимание на приведенные ниже рекомендации по моментам затяжки.
Примечание:
Винты и шайбы переключателя II должны устанавливаться по направлению от задней части к передней с использованием гаек, прикрепленных к соединительным шинам для их удержания. Они ставятся взамен 4 стопорных гаек, первоначально поставляемых в незакрепленном положении вместе с переключателем, поэтому эти 4 дополнительные гайки следует убрать. Винты и шайбы переключателя I следует устанавливать по направлению от передней части к задней с помощью поставляемых незакрепленных гаек в задней части клемм переключателя.
Соединительные шины могут устанавливаться сверху или снизу, как описано выше.
f g e d c
Рекомендуемый момент затяжки (Н∙м)
Максимальный момент затяжки (Н∙м)
Тип винта
Все значения являются приблизительными
от 40 до 125 A
4,5
5,4
M6
16
ATyS S/Sd
— См.: 541 892 C
ATyS S/Sd
6.3.2. Клеммные крышки
Верхняя и нижняя клеммные крышки поставляются для изделий от 40 до 125 А с силовыми соединениями с подходящими кабельными наконечниками до 50 мм². Конструкция клеммных крышек содержит устройство для уплотнения, благодаря которому не требуются какие-либо специальные аксессуары, помимо самого уплотнения.
6.3.2.1. Крышки исходящих клемм (при использовании соединительных шин)
Крышки исходящих клемм сконструированы специально для установки узла соединительной шины 4P и устанавливаются вблизи клемм и исходящих токоведущих частей. Один комплект содержит 2 части, каждая из которых предназначена специально для переключателей 1 и 2. Для упрощения использования изучите приведенные ниже инструкции по установке.
Установка крышек исходящих клемм c c
Снятие крышек исходящих клемм d d c e d e f
ATyS S/Sd
— См.: 541 892 C 17
6.3.2.2. Крышки входящих клемм
Крышки входящих клемм могут устанавливаться на любой стороне изделия (для входящих и исходящих клемм), которая не оснащена соединительными шинами.
Один заказанный комплект содержит 2 идентичные части, установленные спереди, по одной для каждого переключателя.
В комплект крышек клемм входят уплотнительные винты для ограничения доступа к клеммам.
Крышки, установленные на передний переключатель, сконструированы так, чтобы можно было производить термографические измерения без снятия крышки.
Установка крышек входящих клемм
ШАГ 1 ШАГ 2 d c e d c
Снятие крышек входящих клемм
ШАГ 1 c
ШАГ 2 d e d d c c e
6.3.2.3. Уплотнительное устройство для повышения безопасности
Клеммные крышки содержат уплотнительное устройство, полностью интегрированное в конструкцию.
Для упрощения ввода обратите внимание на стрелку, указывающую на направление.
c d e
18
ATyS S / Sd
— Ссылка: 541 892 C
ATyS S / Sd
6.3.3. Рукоятка непосредственного управления и зажим накопителя
AT y S S и AT y S S d содержат рукоятку и зажим накопителя для ручного управления в аварийном режиме. Рукоятка поставляется со стандартным шестигранным телескопическим валом толщиной 8 мм, который устанавливается на передней части AT y S S для безопасного и простого ручного управления. Несмотря на то что вал содержит шпоночный паз, на AT y S S также может устанавливаться стандартный торцовый ключ на 8 мм.
Для повышения безопасности рукоятку можно вставить только в местоположение вала на передней части
AT y S S , когда переключатель режима находится в положении ручного режима.
В маловероятном случае поломки модуля электропривода данный модуль можно снять, как описано ниже
(выкрутив 4 винта). Устройство для управления в аварийном режиме остается полностью функциональным при снятом модуле электропривода. Для этого необходимо снять шестигранный вал с рукоятки, выкрутив центральный крепежный винт на рукоятке. В результате штырьковый шестигранный вал превратится в гнездовую рукоятку непосредственного управления на 10 мм, совместимую с механизмом неизолированного переключателя.
Зажим накопителя рукоятки непосредственного управления в аварийном режиме сконструирован так, чтобы он подходил практически везде:
š Монтаж на DIN-рейку c d
š
Фиксация непосредственно на боковой стороне
AT y S S
š
Фиксация на верхнем или нижнем аксессуаре скобы для защиты разъема.
c d
Одна и та же аварийная рукоятка может использоваться как при установленном, так и при неустановленном электроприводе.
ШАГ 2
ШАГ 1 d c
ШАГ 3 d c
ATyS S/Sd
— Ссылка: 541 892 C 19
7. РАЗЪЕМЫ
7.1. Силовые контуры
7.1.1. Кабельные соединения
Рекомендуемый момент затяжки (Н∙м)
Максимальный момент затяжки (Н∙м)
Тип винта
Все значения являются приблизительными от 40 до 125 A
4,5
5,4
M6
7.1.2. Клеммы для подачи питания от 40 до 125 A или
Альтернативное устройство для облегчения подключения исходящего кабеля. Входящий: исходящие и параллельные подключения могут использоваться вверху или внизу в зависимости от требований заказчика.
я
7.1.3. Площадь поперечного сечения силового кабеля
40 A 63 A 80 A 100 A 125 A
Минимальное сечение кабеля Cu (мм 2 ) при lth
10 16 25
Максимальное сечение кабеля Cu (мм
2
) при lth
70 70
Все значения являются приблизительными.
70
35
70
50
70
22
Примечание по всем данным номинального тока
1
Примите во внимание длину соединительного кабеля при определении его сечения.
Комплект отведения напряжения и клеммных крышек предназначен для использования с наконечниками для кабелей толщиной до 50 мм² и специальных наконечников толщиной до 70 мм .
20
ATyS S/Sd
— См.: 541 892 C
ATyS S/Sd
7.2. Контуры управления
7.2.1. Типичные монтажные схемы AT y S S и AT y S S d
ВНИМАНИЕ
Проверьте, чтобы напряжение питания на дополнительных клеммах для подачи электропитания не превышало пределов. Обращайтесь к информации об ограничении рабочих характеристик в разделе об условиях эксплуатации для выяснения конкретных температур окружающего воздуха.
Максимальная длина управляющего кабеля для клемм 314–317 должна быть ограничена 100 м/800 Ом. При большем расстоянии или сопротивлении добавьте управляющее реле.
ОПАСНО
Не трогайте управляющие или силовые кабели, подключенные к изделию
AT y S, когда может присутствовать или появиться напряжение.
7.2.1.1. AT y S S d: 230 В пер. тока x 2 (сдвоенный источник питания )
Пример: Цепь управления на 415 В пер. тока с использованием изделия AT y S S d, имеющего 3-фазный и нейтральный источник питания и двойной источник питания 2 x 230 В пер. тока.
1
2
Предохр. типа 4A gG
XXXXXXXX
317316315 314
O I II
КОНТРОЛЬ
04 03 24 23 14 13
ДОП. КОНТАКТЫ
ATyS C30
ATyS C40
Управляющие входные сигналы
š Местные или удаленные кнопки.
š Сигналы от контроллера с программируемой логикой.
š
Практически любой контроллер ATS/AMF.
š
Такие контроллеры ATS, как AT y S C30 и AT y S
C40, поставляются компанией SOCOMEC в качестве аксессуара.
š
Контроллеры ATS позволяют автоматизировать переключение между главной и альтернативной подачей. Они также совместимы с удаленными дисплеями/ панелями управления ATyS D10 и ATyS D20.
ATyS S/Sd
— См.: 541 892 C 21
7.2.1.2. AT y S S : 230 В пер. тока
Пример: Цепь управления на 415 В пер. тока с использованием изделия AT y S S , имеющего 3-фазный и нейтральный источник питания, и управляющий источник питания на 230 В пер. тока.
1
2
Предохр. типа 4A gG
XXXXXXXX
317316315 314
O I II
КОНТРОЛЬ
04 03 24 23 14 13
ДОП. КОНТАКТЫ
7.2.1.3. AT y S S : 12 В пост. тока
Пример: Цепь управления на 415 В пер. тока с использованием изделия AT y S S , имеющего 3-фазный и нейтральный источник питания, и управляющий источник питания на 12 В пост. тока.
1
2
Предохр. типа 4A gG
317316315 314
O I II
КОНТРОЛЬ
04 03 24 23 14 13
ДОП. КОНТАКТЫ
22
ATyS S/Sd
— См.: 541 892 C
ATyS S/Sd
7.2.1.4. AT y S S : 24/48 В пост. тока
Пример: Цепь управления на 415 В пер. тока с использованием изделия AT y S S , имеющего 3-фазный и нейтральный источник питания, и управляющий источник питания на 24/48 В пост. тока.
1
2
Предохр. типа 4A gG
317316315 314
O I II
КОНТРОЛЬ
04 03 24 23 14 13
ДОП. КОНТАКТЫ
7.2.1.5. Внешний источник питания (400 В пер. тока)
Силовой трансформатор на 400 В пер. тока, межфазное напряжение, не обеспечивающее доступность нейтрального проводника. Данные трансформатора: 400 В пер. тока – 230 В пер. тока:
50 В·А. (На рисунке приведены данные для AT y S
S на 230 В пер. тока.) Для AT y S S d закажите два трансформатора, подключенных к 101–102 и 201–
202.
101 102
7.2.2. AT y S S RTSE + контроллеры ATS типа AT y S C30 и AT y S C40
Обращайтесь к соответствующему руководству по контроллеру ATS для получения подробных сведений о ATyS C30 и
ATyS C40 e g f
ATyS
D10/D20
f e e g
ATyS
D10/D20
c d c c
Измерение напряжения питания d
Контроль и информация о положении e
Команда «старт/стоп» генератора f
Соединение с интерфейсом ATyS g
Источник питания постоянного тока d c c
Измерение U+F для каждой группы d
Контроль и информация о положении e
Команда «старт/стоп» генератора f
Внешняя команда «старт/стоп» для стандартного цикла g
Источник питания постоянного тока
ATyS S/Sd
— См.: 541 892 C 23
7.2.3. Входные и выходные контакты AT y S S и AT y S S d
Независимые дополнительные контакты
š Пол. I: доп. контакт 13/14
š
Пол. II: доп. контакт 23/24
š Пол. O: доп. контакт 03/04
ATyS s alim 2 sources 230Vac
Команды положения
(нестандартные)
š
Перекл. в пол. II I/P: 314
š
Перекл. в пол. I I/P: 315
š
Перекл. в пол. O I/P: 316
š
Общее: 317
Подключение питания S1, S2, Load
1
2
Параметры источника питания
AT y S S d
Подача пер. тока DPS
XXXXXXXX
AT y S S
Подача пер. тока
AT y S S
Подача пост. тока
7.2.4. Наименование, описание и характеристики клеммы.
Наименование Клеммы Описание Характеристики
Рекомендуемая площадь сечения кабеля
Вход источника питания
Управляющие входные сигналы
Выводы сигнализации
101 Источник питания: L (AT y S S d: 230 В)
102 Источник питания: N (AT y S S d: 230 В)
201 Источник питания: L (AT y S S d: 230 В)
202 Источник питания: N (AT y S S d: 230 В)
301 Источник питания: L (AT y S S : 230 В)
230 В пер. тока
+/- 30 %
(160–310 В пер. тока)
50/60 Гц
302 Источник питания: N (AT y S S : 230 В)
401
402
Источник питания: Положительный + (AT y S S : 12/24/48
В пост. тока)
*12 В пост. тока -25 %/+30 %, остальные +/- 30 %
Источник питания: Отрицательный – (AT
В пост. тока) y
314 Команда положения II, если закрыт с 317
S S : 12/24/48
*12 В пост. тока
(9–15 В пост. тока)
24/48 В пост. тока
(17–62 В пост. тока)
315
316
317
Команда положения I, если закрыт с 317
Команда положения 0, если закрыт с 317
Общая управляющая клемма для 314–316
(источник определенного напряжения)
ВНИМАНИЕ: не подключать с источнику питания
Не изолирован
03
04
Сухой контакт: дополнительный контакт положения 0
Обычно разомкнутый контакт
23
24
Сухой контакт: дополнительный контакт положения I
Обычно разомкнутый контакт
Сухие контакты 2
A AC1/250 В
2 A/24 В пост. тока
13
14
Сухой контакт: дополнительный контакт положения II
Обычно разомкнутый контакт
1,5 мм
1,5 мм
1,5 мм
2
2
2
24
ATyS S/Sd
— См.: 541 892 C
ATyS S/Sd
8. РЕЖИМЫ РАБОТЫ AT
y
S
AT y S включает 3 безопасных и понятных режима работы, выбираемых с помощью переключателя, расположенного на передней стороне изделия. Имеются следующие режимы работы:
š
Автоматический режим:
переключение с дистанционным управлением.
š
Ручной режим:
ручное управление на месте в аварийном режиме.
š
Режим блокировки:
надежное средство для запирания навесным замком.
РЕЖИМ
РЕЖИМ
РЕЖИМ
ШАГ 7B
Ø
3x
4–8 мм
I
NOK ПРОЙДЕН NOK
I I
(((
АВТОМАТИЧЕСКИЙ РЕЖИМ:
š активирует управляющие входные сигналы;
š запрещает использование устройства для навесного замка;
š
запрещает вставку рукоятки для ручного управления в режиме AUT.
Приведение в положение режима AUTO запрещено при навешенном замке или когда рукоятка для ручного управления вставлена в изделие AT y S S .
РУЧНОЙ РЕЖИМ:
š запрещает подачу управляющих входных сигналов;
š позволяет вставить рукоятку для ручного управления в аварийном режиме.
Примечание: обратите внимание на шпоночный паз при вставке рукоятки для аварийного режима в изделие.
Внимание! При ручном управлении убедитесь в том, что индикатор положения помещен в центр окна после приведения в нужное положение.
РЕЖИМ БЛОКИРОВКИ: (с навешенным замком)
š
запрещает подачу управляющих входных сигналов;
š
запрещает вставку рукоятки в аварийном режиме;
š
позволяет использовать
3 навесных замка с диаметром 4–8 мм;
š
позволяет выполнить блокировку, когда на AT y S
S выбрано положение O.
POS 0
ATyS S/Sd
— См.: 541 892 C 25
8.1. Автоматический режим: работа при подаче электропитания
8.1.1. Источник питания
Изделие AT y S S d должно приводиться в действие при подаче питания через клеммы 101 и 102, 201 и 202 с соблюдением следующих ограничений:
š 230 В пер. тока +/- 30 % (160–310 В пер. тока)
š
50/60 Гц +/- 10 %
Изделие AT y S S , версия на 230 В пер. тока, должно приводиться в действие при подаче питания через клеммы 301 и 302 с соблюдением следующих ограничений:
š 230 В пер. тока +/- 30 % (160–310 В пер. тока)
š
50/60 Гц +/- 10 %
Изделие AT y S S , версия на 12 В пост. тока, должно приводиться в действие при подаче питания через клеммы 401 и 402 с соблюдением следующих ограничений:
š 12 В пост. тока – 25 % / + 30 % (9–15 В пост. тока)
Изделие AT y S S , версия на 24/48 В пост. тока, должно приводиться в действие при подаче питания через клеммы 401 и
402 с соблюдением следующих ограничений:
š 24/48 В пост. тока +/- 30 % (17–62 В пост. тока)
XXXXXXXX
XXXXXXXX
Токовый ввод: версии управления с переменным током
š <20 мА (режим ожидания);
š 0,2–0,4 A (режим переключения)
š
0,7–1,25 A для 100 мс (пусковой бросок).
Токовый ввод: версии управления при 12 В пост. тока
š <20 мА (режим ожидания);
š 1,3–1,8 A (режим переключения);
š
5–6,5 A для 100 мс (пусковой бросок).
Токовый ввод: версии управления при 24/48 В пост. тока
š <20 мА (режим ожидания);
š 1,5 A (режим переключения);
š
7–9 A для 100 мс (пусковой бросок).
Концевой разъем (цепь управления):
š минимум 1,5 мм²;
š максимум 2,5 мм².
8.1.2. Ввод команд — описание
Изделие AT y S S содержит 3 входа команд, подаваемых через разъем с 4 контактами. Не следует подавать дополнительное питание на эти контакты, поскольку входы ДОЛЖНЫ использоваться при общем питании с клеммы 317. Эти контакты не заизолированы.
Подача питания на AT y S S должна производиться для активации входов с 314 по 317. Длительность импульса для активации: ≤ 60 мс.
š
Контакт 314. Команда положения II, если закрыт с 317.
Данный контакт активен, когда AT y S S работает в режиме AUT.
Длительность импульса для активации и переключения в положение II равна минимум 30–60 мс.
š
Контакт 315. Команда положения I, если закрыт с 317.
Данный контакт активен, когда AT y S работает в режиме AUT.
Длительность импульса для активации и переключения в положение I равна минимум 30–60 мс.
š Контакт 316. Команда положения O, если закрыт с 317.
Данный контакт активен, когда AT y S работает в режиме AUT.
Длительность импульса для активации и переключения в положение O равна минимум 30–60 мс.
Для логической схемы контактора зафиксировать контакты между клеммами 316 и 317.
š
Контакт 317. Общий для входов 314–316.
26
ATyS S/Sd
— См.: 541 892 C
ATyS S/Sd
8.1.3. Ввод команд — технические данные
š Количество входов для команд: 3 неизолированные входа для команд.
š
Постоянное напряжение: <5 В пост. тока (на любом входе по отношению к земле).
š
Линия постоянного тока:
š Сопротивление линии: от 0,35 до 0,5 мА.
800 Ом.
š Длина линии:
š
Длительность импульса:
š
Концевой разъем:
100 м (минимальное сечение провода 1,5 мм² (#16AWG).
30–60 мс.
минимум 1,5 мм²/максимум 2,5 мм².
8.1.4. Ввод команд — управляющая логика
Операция переключения может выполняться в режиме AUT с помощью внешних контактов, на которых нет напряжения, как описано выше.
В зависимости от конфигурации проводки имеется два типа логики, которые могут применяться к AT y S S .
š Логическая схема импульса.
š
Логическая схема контактора.
Логическая схема ввода AT y S S обеспечивает приоритет командам I и II над O, поэтому логическая схема контактора может реализовываться путем запараллеливания клемм 316 и 317.
Логическая схема импульса.
На AT y S S выбираются стабильные положения (I –
O – II) после получения команды импульса.
š Команда переключения длительностью как минимум 60 мс необходима для запуска операции переключения.
š
Команды I и II имеют приоритет над O.
Логическая схема контактора.
На AT y S S выбирается конкретное положение (I или II), пока подается команда.
š
Подается команда O. (Перемычка 316–317)
š Команды I и II имеют приоритет над O.
š
Команды I и II имеют равный приоритет.
(1-я полученная команда удерживается до тех пор, пока ее подача не прекратится.)
š
Если команда I или II исчезает, устройство выполняет возврат в нулевое положение
(при подаваемом электропитании).
команда I команда 0 команда II положение I положение 0 положение II
Импульс ≥ 60 мс
удерживается
(Примечание: исключаются задержки переключения положения) команда I команда 0 команда II положение I положение 0 положение II
Импульс ≥ 60 мс
удерживается
(Примечание: исключаются задержки переключения положения)
8.1.5. Выходы сухого контакта — дополнительные
Изделие AT y S оснащено интегрированными дополнительными контактами вывода с независимым положением (I – O – II) , осуществляемого через 3 микропереключателя.
Энергия должна подаваться на сухие контакты пользователем.
š
Контакты 13–14, 23–24, 03–04
(обычно открытые и независимые контакты)
ATyS S/Sd
— См.: 541 892 C 27
š Количество дополнительных контактов: 3.
š
Конфигурация: НЕТ.
š
Механическая износостойкость: 100 000 циклов.
š Номинальное напряжение/переключающее напряжение: 250 В пер. тока/24 В пост. тока/48 В пост. тока.
š Номинальный ток:
š
Выходные клеммы:
2 A.
минимум 1,5 мм²/максимум 2,5 мм².
8.2. Ручное управление
Изделием AT y S S можно управлять вручную как оборудованием с ручным переключением (MTSE) с сохранением электрических характеристик и эффективности функции переключения питания. Данная функция обычно используется в случае аварии или при техническом обслуживании.
Для управления изделием AT y S S вручную убедитесь в том, что нет доступа к токоведущим частям, переведите передний переключатель в положение ручного управления (рис. 4.1, элемент 11) и вставьте рукоятку (рис.
4.1, элемент 7) в отверстие для вала рукоятки для работы в аварийном режиме (рис. 4.1, элемент 10). Место вставки вала содержит шпоночный паз для размещения рукоятки в правильном положении.
Поворачивайте рукоятку на 60° по часовой стрелке или против часовой стрелки (в зависимости от нужного положения), чтобы последовательно изменять ее положение.
I
Æ
O На 60° по часовой стрелке
I
II
Æ
Æ
O
O
Æ
II На 60° + 60° по часовой стрелке
На 60° против часовой стрелки
II
Æ
O
Æ
I На 60° + 60° против часовой стрелки
60
°
60
°
Внимание! При ручном управлении убедитесь в том, что индикатор положения помещен в центр окна после приведения в нужное положение.
Не пройден
Пройден Не пройден
I I I
ВНИМАНИЕ
Проверьте положение и направление вращения изделия перед активацией ручного режима работы.
Снимите рукоятку с изделия перед переводом переключателя в положение
AUT или для блокировки.
8.3. Блокировка
Изделие AT y S S можно заблокировать в положении O, используя до 3 навесных замков.
Чтобы заблокировать изделие AT y S S , сначала убедитесь в том, что рукоятка ручного управления не вставлена в установочное отверстие, затем переведите передний переключатель в положение блокировки.
Потяните механизм блокировки наружу, чтобы открыть гнездо для вставки навесных замков.
Заблокируйте устройство, используя утвержденные качественные навесные замки с минимальным диаметром 4 мм и максимальным диаметром 8 мм. В механизм блокировки изделия AT y S можно вставить максимум 3 замка с толщиной дужки 8 мм.
ВНИМАНИЕ
Вставка замков разрешена в положении «O» в режиме блокировки, если рукоятка для аварийного режима не вставлена в установочное место вала.
28
ATyS S/Sd
— См.: 541 892 C
ATyS S/Sd
9. ХАРАКТЕРИСТИКИ AT
y
S
S
Характеристики согласно стандартам IEC 60947-3 и IEC 60947-6-1
От 40 до 125 A
Тепловой ток I th
при 40°C
Номинальное напряжение по изоляции U i
(В) (силовая цепь)
Максимально допустимое импульсное напряжение U imp цепь)
(кВ) (силовая
Номинальное напряжение по изоляции U i
(В) (рабочий контур)
Максимально допустимое импульсное напряжение U imp контур)
(кВ) (рабочий
40 A
800
6
300
4
Номинальный рабочий ток I e
(A) согласно стандарту IEC 60947-3
Номинальное напряжение Категория использования A/B
415 В перем. тока
415 В перем. тока
415 В перем. тока
415 В перем. тока
AC-20 A/AC-20 B
AC-21 A/AC-21 B
AC-22 A/AC-22 B
AC-23 A/AC-23 B
40/40
40/40
40/40
-/40
Номинальный рабочий ток I e
(A) согласно стандарту IEC 60947-6-1
Номинальное напряжение Категория использования A/B
415 В перем. тока
415 В перем. тока
AC-31 B
AC-32 B
40
40
63 A
800
6
300
4
A/B
63/63
63/63
63/63
-/63
A/B
63
63
80 A
800
6
300
4
A/B
80/80
80/80
80/80
-/63
A/B
80
80
Стойкость к короткому замыканию (среднеквадратичный прогнозируемый ток, кA)
Ожидаемый ток к.з. (кА, действующее значение)
Соответствующий номинальный ток предохранителя (A)
Прерыватель цепи для защиты от короткого замыкания обеспечивает отключение менее чем за 0,3 с
(1)
Ном. кратковременно допустимый ток 0,3 с I cw
(кA ср. кв.)
Способность замыкания цепи (без защиты)
3,5 3,5 3,5
Ном. кратковременно допустимый ток 1 с I
CW
(кA ср. кв.)
Номинальная способность замыкания цепи
Разъем
Максимальное сечение медного кабеля (мм
2
)
Момент затяжки мин./макс.(Нм)
50
40
2.5
4.5
50
1,2/3
50
63
2.5
4.5
50
1,2/3
50
80
2.5
4.5
50
1,2/3
Время переключения (стандартная настройка)
I – O или II – O (мс)
I – II или II – I (мс)
Длительность отключения электричества I – II (мс) минимум
Источник питания
Подача питания 12 В пост. тока мин./макс. (В пост. тока)
Подача питания 24/48 В пост. тока мин./макс. (В пост. тока)
Подача питания 230 В перем. тока мин./макс. (В перем. тока)
Потребность мощности питания цепи управления
Подача питания 12 В пост. тока, при броске тока/номинальное (ВА)
Подача питания 24/48 В пост. тока, при броске тока/номинальное (ВА)
Подача питания 230 В перем. тока, при броске тока/номинальное (ВА)
Механические характеристики
Срок службы (число рабочих циклов)
Вес ATyS S и ATyS Sd 4 P (кг)
500
1000
500
9/15
17/62
160/310
200/40
200/40
200/40
10 000
3
500
1000
500
9/15
17/62
160/310
200/40
200/40
200/40
10 000
3
500
1000
500
9/15
17/62
160/310
200/40
200/40
200/40
10 000
3
100 A
800
6
300
4
A/B
100/100
100/100
100/100
-/63
A/B
100
80
25
100
3,5
2.5
4.5
50
1,2/3
500
1000
500
9/15
17/62
160/310
200/40
200/40
200/40
10 000
3
125 A
800
6
300
4
A/B
125/125
100/125
100/100
-/63
A/B
125
80
15
125
3,5
2.5
4.5
50
1,2/3
500
1000
500
9/15
17/62
160/310
200/40
200/40
200/40
10 000
3
(1) Значение для согласования с любым прерывателем цепи, который обеспечивает отключение менее чем за 0,3 с. Для согласования с указаниями на конкретный прерыватель цепи доступны более высокие значения тока короткого замыкания. Обращайтесь к нам.
ATyS S/Sd
— См.: 541 892 C 29
10. РУКОВОДСТВО ПО ПОИСКУ И УСТРАНЕНИЮ
НЕИСПРАВНОСТЕЙ
AT y S S не работает при подаче электропитания š Убедитесь в том, что напряжение электропитания, подаваемого на клеммы от 101 до 402, находится в приемлемых пределах соответственно конкретному устройству и его номинальному напряжению.
12 В пост. тока: 9–15 В пост. тока;
24/48 В пост. тока: 17–62 В пост. тока;
230 В пер. тока: 160–310 В пер. тока.
š Убедитесь в том, что передний переключатель находится в положении (AUT).
š
Убедитесь в том, что клемма контакта и сигналы контакта находятся в диапазоне от 314 до 317.
Обычно открытые контакты с приоритетом для сигналов I и II.
Невозможно эксплуатировать переключатель в ручном режиме
š Убедитесь в том, что передний переключатель находится в положении ручного управления.
š Убедитесь в том, что изделие не заблокировано.
š Проверьте направление вращения рукоятки.
š
Окажите достаточное непрерывное воздействие в направлении, указанном на AT y S S .
Работа при подаче электроэнергии не соответствует внешней команде I, O, II
Невозможно заблокировать
Изделие не реагирует на удаленные команды
Техобслуживание
š
Проверьте проводку выбранной управляющей логики (импульс или контактор)
Импульс > 60 мс
314–317: Переключить в положение «II».
315–317: Переключить в положение «I».
316–317: Переключить в положение «0».
Обслуживается — перемычка
316–317: Логика контактора (вернуть на ноль).
š
Убедитесь в том, что передний переключатель находится в положении блокировки.
š
Убедитесь в том, что рукоятка ручного управления в аварийном режиме не вставлена в гнездо ручного режима AT y S S .
š
Убедитесь в том, что на изделии AT y S S выбрано положение «0».
š
(Блокировка возможна только в положении «0» при снятой рукоятке ручного управления в аварийном режиме.)
š Переведите изделие в ручной режим и переключите в нулевое положение, используя рукоятку аварийного режима.
š
Переключите с ручного на автоматический режим в нулевом положении.
š Убедитесь в том, что подаваемое дополнительное напряжение AUX находится в нужных пределах.
š Убедитесь в том, что удаленные сигналы принимаются.
š
Рекомендуется по крайней мере один раз в год осуществлять полный цикл работы переключателя в автоматическом или ручном режиме.
30
ATyS S/Sd
— См.: 541 892 C
11. ЗАПАСНЫЕ ЧАСТИ И АКСЕССУАРЫ
11.1. Аксессуары
Клеммные крышки на стороне источника
Клеммные крышки на стороне нагрузки
См.: 9594 4012
Комплект для отвода напряжения: верхний/нижний
См.: 9594 9012
Соединительные шины: возможна установка вверху или внизу
ATyS S/Sd
См.: 9599 4001
Скоба для легкой защиты коннектора
См.: 9509 4012
Модуль DIN-рейки 4
Скоба для легкой защиты коннектора состоит из части, которая закрепляется непосредственно в модуле электропривода AT y S S (основание), и части, которая обжимает, удерживает и защищает средство управления, дополнительный контакт и дополнительные разъемы для подачи питания. Кроме того, что данный фиксатор легко устанавливается и закрепляется для защиты разъемов, его очень легко снимать без применения специального инструмента.
См.: 9599 4002
См.: 9599 4003
11.2. Запасные части AT
y
S
S
11.2.1. Модуль электропривода
Замена электропривода и средств управления легко производится в рабочем режиме путем выполнения следующих простых действий:
š
отсоедините зеленые разъемы (проводка для управления, дополнительного питания и дополнительных контактов);
š открутите 4 винта на передней стороне ATyS S;
š осторожно снимите модуль электропривода.
Для установки нового модуля электропривода выполните следующие действия:
š
установите модуль электропривода на переключателе, используя вал ручного управления на переключателе как установочный ключ (при установке электропривода убедитесь в том, что переключатель и модуль электропривода находятся в одном и том же положении
(I – 0 или II));
š
закрутите 4 первоначально приложенных винта в нужных местах и затяните их с рекомендуемым крутящим моментом;
š подсоедините зеленые разъемы.
ОПАСНО
Только 4 винта
Никогда не трогайте установленные заказчиком аксессуары, поскольку существует риск наличия или появления напряжения.
ATyS S/Sd
— См.: 541 892 C 31
Запасные части модуля электропривода
AT y S S d
230 В пер. тока x2
AT y S S
230 В пер. тока
AT y S S
24/48 В пост. тока
AT y S S
12 В пост. тока
9513 5004
9513 5006
9513 5008
9513 5010
9513 5012
9503 5004
9503 5006
9503 5008
9503 5010
9503 5012
9506
5004
9506
5006
9506
5008
9506
5010
9506
5012
9505
5004
9505
5006
9505
5008
9505
5010
9505
5012
40 A
63 A
80 A
100 A
125 A
40 A
63 A
80 A
100 A
125 A
40 A
63 A
80 A
100 A
125 A
40 A
63 A
80 A
100 A
125 A
11.2.3. Запасные переключатели питания: AT y S S и AT y S S d
40 A
63 A
80 A
100 A
125 A
9509 1004
9509 1006
9509 1008
9509 1010
9509 1012
11.2.4. Рукоятка непосредственного ручного управления в аварийном режиме
11.2.5. Монтажные ножки
9599 5012
X2
X2
9599 0001
32
ATyS S/Sd
— См.: 541 892 C
ATyS S/Sd
11.2.6. Набор концевых разъемов
Для всех моделей ATyS S/Sd
X5 xxxx XXXX
12. ИНФОРМАЦИЯ О ЗАКАЗЕ AT
y
S
S
и AT
y
S
S
d
Ниже приводится руководство по заказу переключателей с электроприводом AT y S S и AT y S S d, поставляемых вместе с рукояткой для аварийного режима и зажимом накопителя. Данное руководство содержит объяснение логики назначения регистрационных номеров SOCOMEC AT y S S .
При создании заказа обращайтесь к последнему каталогу SOCOMEC.
95 0 5 4 006
Продукт
95 – TSE: I – O – II
Тип
0 – одинарная дополнительная подача
1 – двойная дополнительная подача (DPS)
Управляющее напряжение
3 – 230 В пер. тока
5 – 12 В пост. тока
6 – 24/48 В пост. тока
№ полюсов
Полюс 4-4
Номинальный ток
004 — 40 A
006 — 63 A
008 — 80 A
010 — 100 A
012 — 125 A
Номинальный ток lth при 40° C
12.1. Регистрационные номера каталога AT
y
S
S
и AT
y
S
S
d
AT
y
S
S
Номинальный ток
40 A
63 A
80 A
100 A
125 A
кВА при
415 В пер. тока
≤ 28 кВА
≤ 45 кВА
≤ 57 кВА
≤ 70 кВА
< 90 кВА
№ полюсов
4
4
4
4
4
AT
y
S
S
12 В пост. тока
9505 4004
9505 4006
9505 4008
9505 4010
9505 4012
AT
y
S
S
24/48 В пост. тока
9506 4004
9506 4006
9506 4008
9506 4010
9506 4012
AT
y
S
S
230 В пер. тока
9503 4004
9503 4006
9503 4008
9503 4010
9503 4012
AT
y
S
S
d
230 В пер. тока x2
9513 4004
9513 4006
9513 4008
9513 4010
9513 4012
ATyS S/Sd
— См.: 541 892 C 33
во всем мире
РОССИЯ
Critical Power / Power Control & Safety /
4-ая ул. 8 Марта, 6А, 407
125167 — Москва
Тел. 495 775 19 85 факс 495 775 19 85 [email protected]
В ЕВРОПЕ
БЕЛЬГИЯ
Critical Power / Power Control & Safety / [email protected]
ВЕЛИКОБРИТАНИЯ
Critical Power [email protected]
Power Control & Safety / Energy Efficiency [email protected]
ГЕРМАНИЯ
Critical Power [email protected]
Power Control & Safety / Energy Efficiency [email protected]
ИСПАНИЯ
Critical Power / Power Control & Safety / [email protected]
ИТАЛИЯ
Critical Power inf[email protected]
Power Control & Safety / Energy Efficiency [email protected]
Solar Power [email protected]
НИДЕРЛАНДЫ
Critical Power / Power Control & Safety / [email protected]
ПОЛЬША
Critical Power [email protected]
Power Control & Safety / Energy Efficiency [email protected]
ПОРТУГАЛИЯ
Critical Power / Solar Power [email protected]
РУМЫНИЯ
Critical Power / Power Control & Safety / [email protected]
СЛОВЕНИЯ
Critical Power / Power Control & Safety / [email protected]
ТУРЦИЯ
Critical Power / Power Control & Safety / [email protected]
ФРАНЦИЯ
Critical Power / Power Control & Safety / [email protected]
В АЗИАТСКО-
ТИХООКЕАНСКОМ РЕГИОНЕ
АВСТРАЛИЯ
Critical Power / Power Control & Safety [email protected]
ВЬЕТНАМ
Critical Power [email protected]
ИНДИЯ
Critical Power [email protected]
Power Control & Safety / Energy Efficiency [email protected]
Solar Power [email protected]
КИТАЙ
Critical Power / Power Control & Safety /
Energy Efficiency [email protected]
СИНГАПУР
Critical Power / Power Control & Safety /
Energy Efficiency [email protected]
ТАИЛАНД
Critical Power [email protected]
НА БЛИЖНЕМ ВОСТОКЕ
ОБЪЕДИНЕННЫЕ АРАБСКИЕ
ЭМИРАТЫ
Critical Power / Power Control & Safety / [email protected]
В АМЕРИКЕ
США КАНАДА МЕКСИКА
Power Control & Safety / Energy Efficiency [email protected]
ДРУГИЕ СТРАНЫ
СЕВЕРНАЯ АФРИКА
Алжир / Марокко / Тунис [email protected]
АФРИКА
Другие страны [email protected]
ЮЖНАЯ ЕВРОПА
Кипр / Греция / Израиль / Мальта [email protected]
ЮЖНАЯ АМЕРИКА [email protected]
ПОДРОБНЕЕ www.socomec.ru/worldwide
ГОЛОВНОЙ ОФИС
ГРУППА SOCOMEC
SAS SOCOMEC капитал 10 951 300 €
R.C.S. Strasbourg B 548 500 149
B.P. 60010 — 1, rue de Westhouse
F-67235 Benfeld Cedex — FRANCE
Тел. +33 3 88 57 41 41 факс +33 3 88 74 08 00 [email protected]
www.socomec.ru
ВАШ ДИСТРИБЬЮТОР
-
Installation and operating manual
-
Installation and operating manual
-
Installation and operating manual
-
Installation and operating manual
-
Installation and operating manual
-
Installation and operating manual
-
Installation and operating manual
-
Installation and operating manual
-
Installation and operating manual
-
Installation and operating manual
-
Installation and operating manual
-
Installation and operating manual
-
Installation and operating manual
-
Installation and operating manual
-
Installation and operating manual
-
Installation and operating manual
-
Installation and operating manual
-
Installation and operating manual
-
Installation and operating manual
-
Installation and operating manual
-
Installation and operating manual
-
Installation and operating manual
-
Installation and operating manual
-
Installation and operating manual
-
Installation and operating manual
-
Installation and operating manual
-
Installation and operating manual
-
Installation and operating manual
-
Installation and operating manual
-
Installation and operating manual
Реле автоматического включения резервного питания ATyS C30
Реле контроля ATyS C30 предназначено для автоматического или ручного переключения нагрузки с основного источника питания на резервный. В случае если резервным источником является дизель-генератор , то подается сигнал на его запуск. Данный прибор позволяет управлять различными силовыми коммутационными устройствами (переключатель нагрузки с моторприводом , контактор,автоматические выключатели с моторприводами и т.д.). В основной сети осуществляется контроль напряжения трех фаз,частота,обрыв фазы ,чередование фаз. В резервной сети осуществляется контроль напряжения одной фазы частота ,контроль чередования фаз. К реле контроля возможно подключение интерфейса удаленного управления ATyS D10 или D20 .
Основные характеристики прибора
- Напряжение питания от измеряемой сети (под заказ -с питанием 24VDC)
- Диапазон контролируемого напряжения 110…400 VAC/10%
- Задаваемые уставки напряжения
нижний предел 0,8…0,9 Ue
верхний предел 1,02…1,2 Ue
- Задаваемые уставки частоты
нижний предел 0,8…0,99 F
верхний предел 1,01…1,2 F
Время переключения определяется значениями устанавливаемых задержек ,каждая из которых характеризует скорость отдельной операции (от 0с до 30мин.).
Реле имеет два программируемых входа и два программируемых выхода.
Доставка по городам Крыма: Симферополь, Севастополь, Феодосия, Ялта, Алушта, Евпатория, Саки, Керчь, Армянск, Джанкой, Бахчисарай, Красноперекопск, Красногвардейское, Советское, Первомайское, Кировское и др. городам России
Automatic Transfer Switchfrom 63 to 3200 A
Modular Automatic Transfer Switchfrom 63 to 160 A
CHANGEOVERTwo mechanically interlockedpower switches.
OPERATIONA configurable automatic controlassociated with an emergencymanual operation.
MONITORING &CONTROLA built-in configuration and controlinterface, simple or advanced.
INSTALLATIONA modular product adapted to anytype of enclosure integration. at
ysm
_007
_a
ADAPTED RANGE
> ATyS M 6s: simple and ergonomicConfigurable automatic transfer switch cycles, with stable positions.
> ATyS M 6e: advanced and programmableFully programmable automatic transfer switch cycles ensuring position stability or return to 0 position feature upon loss of network.
atys
m_0
31_b
atys
m_0
30_b
ATyS M proposes a complete range of products to meet all breakbefore make transfer requirements.
atys
m_0
29_b
> ATyS M 3s: remote controlled switch
A PRODUCT FOR ALL CHANGEOVER APPLICATIONS FROM 63 TO 160 A> Network/Generator Set• Generator set control
Non-criticalloads
ATyS M 3sGS
Criticalloads
UPS
• ATS solution
Non-criticalloads
ATyS M 6sATyS M 6e GS
Criticalloads
UPS
> Network/Network• Building services
ATyS M 6e
ATyS M 6s
• Control with or without priority
Non-criticalloads
ATyS M 6e
Criticalloads
UPS
atys
m_0
03_a
_gb
atys
m_0
04_a
_gb
atys
m_0
05_a
_gb
atys
m_0
06_a
_gb
Changeover switches
A. 2
AN OPTIMISED SWITCHING SYSTEM> Switching technology• An on load switch disconnector providing
safety isolation combined with high makingand breaking characteristics
• Safety isolation• Stable positions
> A new switching module combining• High dynamic withstand• Fast operation• High number of operations
> Two power switchesMechanically and electricallyinterlocked SIISI
tays
m_0
02_a
atys
m_0
38_a
> Bridging bar
A COMPLETE RANGE OF ACCESSORIES
atys
m_0
19_a
atys
m_0
27_a
atys
m_0
21_a
atys
m_0
35_a
FAST ELECTRICAL OPERATION> Electromagnetic controlEnables fast I — II switching operation
> An available energy storagedevice
Enables return to 0 position featureupon loss of network without anypower source available
atys
m_0
37_a
OPERATION
> Automatic/Manualoperating modeselection via theprotective cover
> Operation using a standard allenkey
> Padlocking func-tion configurablein position 0 or inall three positionsI — 0 — II
FLEXIBLE INTEGRATION
ATyS M integrated into a modular DIN enclosure (Din rail or backplate mounted).
appl
i_17
9_b
appl
i_17
7_a
Network failure
Automatic mode (AUT)
Generator start
MFT
Network availability
Switch to position 0
Switch to position
Switch to position
Generator stop
Switch to position 0
Semi automatic mode
Network availability
DTT
0MFMRT
0MR
CDT
no
yes
Manualoperation
Network : priority power sourceNetwork : backup power source2
1
2
1
2 1
1
Example (generator application):
A DEDICATED CONTROL LOGIC
atys
_028
_c_g
b
atys
_565
_c
> Voltage tap
> Auxiliary contacts > Terminal shrouds
atys
m_0
14_b
_1_c
at
atys
m_0
15_b
_1_c
at
atys
m_0
16_b
_1_c
at
atys
m_0
33_a
_1_c
at
> Sealable cover (ATyS M 6s)
> Remote display (ATyS M 6e)
A. 3
ATyS M 3s ATyS M 6s ATyS M 6e63 to 160 A 63 to 160 A 63 to 160 A
Normal/backup transfer with an external automatic control •Normal/backup transfer with an internal automatic control (ATS) • •Load changeover •External controller: Main/Main or Genset/Main applicationsExternal controller: Dual genset application
AUXILIARY POWER SUPPLYVersion 1 AC power supplyVersion 2 AC power supplies •Version 1 DC power supply
OPERATIONVolt free auxiliary contacts for the I, 0, II positions •Automatic for I, 0, II positions • •MAN / AUT selector switch • • •
MONITORING Main network : 3U • •Emergency network : 3U • •Main network: 1UEmergency network : 1U
CONFIGURATIONChoice of logic: contactor or impulse •Upper and lower thresholds, associated hysteresis • •Operating time delays • •Network priority • •
FRONT DISPLAYStatus of supplies, positions, commands, faults, padlocking • •U •F •3I, P, Q, S, PF, In monitored
CONTROL / OPERATIONPosition I and II auxiliary contacts accessory accessory accessoryPosition 0 auxiliary contacts accessory accessory accessoryPadlock and MAN / AUT information auxiliary contacts •Generator start-up output auxiliary contacts • •Fault relay output auxiliary contacts • •RS485 (JBUS MODBUS®) — accessory2 input / 2 output — accessory
REMOTE INTERFACE (ACCESSORY)ATyS D10 display device •ATyS D20 display and control device •
SOCOMEC general catalogueA. 4
SELECTION GUIDE
ATyS 63 to 3200 A
A P P L I C AT I O N S
atys
m_0
07_a
_2_c
at
atys
m_0
12_a
_2_c
atPower
Command
Load
M
Example: between atransformer and a genset
see page
A.12see page
A.12see page
A.12
C H A R A C T E R I S T I C S
PA G E S
Changeover switches
atys
m_0
13_a
_2_c
at
SOCOMEC general catalogue A. 5
atys
_003
_a_3
_cat
atys
_103
_a_1
_cat
atys
_097
_b_2
_cat
atys
_102
_a_2
_cat
atys
_448
_b_2
_cat
atys
_599
_b_2
_cat
ATyS 3s ATyS 3e ATyS 6e ATyS 6m ATyS C30 ATyS C40125 to 1800 A 125 to 3200 A 125 to 3200 A 125 to 3200 A
• •• •
• ••
•
•• • • •
• •
• • • •• •
• • • •
• • •• •
•• •
• • • • • •• • • •• • • •• • • •
• • • • •• •• •
•
• • • •• • •• • •
• • • •• •
accessory accessoryaccessory accessory • (std)
• • •• • •
acce
s_20
5_a_
1_ca
t
Bridging bars
atys
_606
_a_2
_cat
Voltage sensingand powersupply kit
see page
A.38see page
A.36see page
A.36see page
A.12see page
A.12see page
A.12see page
A.12
see page
A.17
Remote interface
atys
_565
_c_2
_cat
ATyS VISIONsoftware
couv
_128
_a_2
_cat
A. 6
Changeover switches
The ATyS range
SOCOMEC general catalogue
The ATyS remote controlled and automatic transfer switch familyproposes a complete range of low voltage compact changeoverswitches and accessories.The new ATyS M family dedicated to applications below 160 Aretains key features and characteristics of the existing ATySproduct range bringing some innovation.
ATyS range is now also available up to 3200A to complete thefamily for higher current applications.
ATyS are composed of two mechanically and electricallyinterlocked switches.All the products are fitted with emergency manual operation.
• either remotely controlled: ATyS M 3 and ATyS 3 products aredriven by volt-free dry contacts allowing switching operationbetween position I, 0 or II, from an external control logic or a plc(control relays type ATyS C30).
• or automaticaly controlled: ATyS M 6 and ATyS 6 arededicated to break before make automatic transfer applications.They integrate control relays, timers and test functions tomanage a Normal/Backup switching operation between 2networks or a generator set and a network.
OverviewOperating principle
�
Network failure
Automatic mode (AUT)
Generator start
MFT
Network availability
Switch to position 0
Switch to position
Switch to position
Generator stop
Switch to position 0
Semi automatic mode
Network availability
DTT
0MFMRT
0MR
CDT
no
yes
Manualoperation
Network : priority power sourceNetwork : backup power source2
1
2
1
2 1
1
Example (generator application):
atys
_028
_c_1
_gb_
cat
Normal / Emergency Timers
• MFT: Main failure timer (0-60s)• DTT: Delay to transfer on Generator set timer (0-60s)• 0MF: 0 position stay before transfer on Generator set (0-20s)• MRT: Main return timer before retransfer (0-30min.)• 0MR: 0 position stay before re transfer on Main (0-20s)• CDT: Cool down timer before Generator set shutdown (0-10 min).
AUT/ MAN sealable coverOpening the front cover disableselectrical or automatic operations andenables manual or padlocking facilities.
Indication of the front cover status(opened or closed) is available on theATyS M via a dedicated auxiliarycontact.
Padlocking facilityIt is possible as standard to padlock theATyS M product in 0 position. 3 positions padlocking is configurable onthe product before its installation.
atys
m_0
16_b
_1_c
at
atys
m_0
14_b
_1_c
at
Manual operation
�
Emergency manual operationATyS M products can be manuallyoperated in any of the three availablepositions (I,0,II) using a standard allenkey provided once the cover is opened.
atys
m_0
15_b
_1_c
at
Description
�
ATyS M: Modular automatic transfer switches from 63 to 160 A
ATyS M electrical operation utilises coil technology to achieve fasttransfer cycles.ATyS M 6e brings a new innovative solution allowing thechangeover to be driven into 0 position without any power supplyavailable.
�
The ATyS rangeATySATyS C30 / ATyS C40ATyS VISION softwareOther changeover switches
A. 7
Changeover switches
The ATyS range
SOCOMEC general catalogue
Power supply
�
Command
�
ATyS M 3s: Remote controlled changeover
Positions command is realised via external volt free contacts(example ATyS C30 controller). Position remains stable in case ofpower supplies loss (switch technology).
Impulse control mode
• A minimum 30 ms impulse required.• I and II commands have priority over 0 command (different from
ATyS).• The first command (order) received has priority for its duration.
Contactor control mode
• The 0 command must be maintained to enable contactor controlmode (strap between 0 / C command and common terminal).
• In case of position I or position II command loss, the productreturns to position 0 (only if the required power input to allow theoperation is available).
ATyS M 3s is equipped with two independent 230 VAC (176-288 VAC), 50/60 Hz (45-65 Hz) power inputs.• These two supplies can be individually connected to source
I and source II power inputs:- Power supply I must be available to reach position I- Power supply II must be available to reach position II.
The 0 position is in this type off control scheme only a transitoryposition.• Use of a SOCOMEC DPS unit (Double Power Supply), or of an
independent power supply will allow control of the product inany of the three positions as soon as power is available on theproduct power inputs.
Wiring diagram
�
1 : control position I2 : control position II3 : control position 0 / C4 : power supply I (230 VAC)5 : power supply II (230 VAC)6 : voltage tap
A: bridging bar (accessories)B : single phase voltage sensing tap (accessories)C : auxiliary contacts — 1 AC per position I, 0, II ( accessories)D : F1 / F2 = fuse 10 A gG.
101102201202313314315317
A
BBBB
C
3
5
4
6 6 6 6
21 D
or
atys
m_0
40_c
_1_x
_cat
atys
m_0
29_b
order I
order O
order II
position I
position O
position IIatys
m_0
42_a
_1_g
b_ca
t
atys
m_0
25_a
_1_c
at
Bridging barTo provide a common connection pointon the load side:- insulated IP2x- leaves the cable terminals free by using
a dedicated fixing location.
atys
m_0
26_a
_1_c
at
Single phase voltage sensing tapAllows up to 2x 1.5 mm2. sensing cablesconnection on main power terminalskeeping power cables capacitycomplete. They can be mounted in anyof the power terminals but notsimultaneously with the bridging bar.
atys
m_0
27_a
_1_c
at
Terminal shroudProvides protection against directcontact with the connection terminals orparts. A specific front hole enablesaccess to terminals’ tightening screwsfor thermographic measurement orvoltage sensing.The same accessory can be mounted onthe incoming or outgoing side of theproducts.
Main accessories
�
atys
m_0
28_a
_1_c
at
Auxiliary contactsEach product can be equipped with 2 auxiliary contacts. It integrates oneNO/NC contact per position (I, 0, II).Characteristics: 250 VAC — 5A maximum.
atys
_565
_c_2
_cat
Remote interfaces ATyS D10 or D20To display source availability andchangeover state on the front of a panel.RJ45 cable connection between ATyS M 6e only, and ATyS D10 / D20.
atys
m_0
43_a
Sealable coverControls settings cover to avoid ATyS M 6s parameters access due to a sealable facility.
A. 8
Changeover switches
The ATyS range
SOCOMEC general catalogue
ATyS M 6: Automatic Transfer Switch
Wiring diagram
�
210209208207 74736463
A
B
ATyS M 6s ATyS M 6e
312
76
210209208207 54534443
312
54
74736463
76
RJ
8
1 2
priority sourcebackup source
ATyS M 6s1 : manual retransfer / priority change2 : test on load3 : automatic mode inhibition6 : fault relay7 : genset start / stop relay
ATyS M 6e1 — 2 — 3 : programmable input4 : “non automatic” mode output5 — 6 : programmable output7 : genset start / stop relay8 : RJ 45 ATyS D10/D20 remote interface connection
A: bridging bar (accessory)B : auxiliary contacts (accessory) — 1 AC per position I, 0, II.
2
1
atys
m_0
41_b
_1_x
_cat
4 potentiometers• Nominal voltage configuration.• Voltage and frequency thresholds configuration.• Operating cycles timers configuration: MFT (0 to 60s), DTT (5s),
MRT (0 to 30 min), CDT (4 min).4 dip switches50 or 60 Hz, single or three phases, 2 seconds 0 positiontransition during I-II transfer cycles (0MR/0MF), Network / Networkor Network / Genset application.4 ledsPower supply sources availability; Automatic mode (coveropened); Fault (command order and position not reached).3 external command inputs• Automatic mode inhibition.• Remote test on load (or priority change).• Manual retransfer from emergency source to main source
(validation required).1 NO bi-stable output relay for generator start /stop command(30 VDC / 2 A).1 NO fault relay (250 VAC/ 0,5 A).
ATyS M 6s ATyS M 6e
Operation
�
atys
m_0
31_b
Display + Keypad• Parameters configuration (thresholds, timers …).• 3 phases voltage and frequency for source I and II, timers,
number of cycles and last event display.• Tests and positions control facilities.LedsPower On; Sources availability; Changeover position; “MAN / AUT”mode; Test / Control operation; Fault.3 configurable inputsAutomatic mode inhibition; Test on load and off load; Manualretransfer; Changeover position control; Network priority change.1 NO bi-stable output relay for generator start /stop command(30 VDC / 2 A).
2 programmable output relays (250 VAC / 3 A)Source I or II availability; Load shedding output; Fault relay.
ATyS D10 or D20 remote interface connection.
atys
m_0
30_b
Characteristics
�
Power supplyATyS M 6 products are self power supplied from incomingsupplies: 230 VAC (176-288 VAC), 50/60 Hz (45-65 Hz).Two different versions are available:• 230 / 400 VAC with neutral conductor distributed: product is
power supplied between phase and neutral.• 127 / 230 VAC with or without neutral conductor distributed:
product is power supplied between 2 phases.The neutral conductor can be connected to the left or right side ofeach switch.
Return to 0 position feature (only on ATyS M 6e)With ATyS M 6e it is possible to return automatically to the 0position after a power supply loss. An energy storage device enables return to the 0 position evenwith no voltage available on the power supply inputs.
Single phase or three phases voltage and frequency controlon networks I and II
ATyS M 6s• Linked over/under voltage and over/under frequency thresholds
from 5 to 20% of Un and 3 to 10% of fn.• Hysteresis levels fixed at 80% of the set up threshold.
ATyS M 6e• Independent over/under voltage and over/under frequency
thresholds +/-20% of nominal values.• Configurable associated hysterisis thresholds.• Phase rotation and unbalance control.
Metering only on ATyS M 6e• 3 phases voltage measurement on networks and .• Frequency measurement on networks and .• Timers display and count down.
21
21
�
The ATyS rangeATySATyS C30 / ATyS C40ATyS VISION softwareOther changeover switches
A. 9
Changeover switches
The ATyS range
SOCOMEC general catalogue
ATyS: from 125 to 3200 ADescription
�
Power supply
�
ATyS products are mechanically interlocked, back to backmounted, load break switches. Their compact design guaranteesposition stability and high dynamic withstand.
Simplified diagram• ATyS 3s: one power input 230 VAC (176-288 VAC), 50/60 Hz (45-65 Hz).
• ATyS 3e, 6e, 6m: two power inputs VAC (176-288 VAC), 50/60 Hz(45-65 Hz), one defined as power source and the other asbackup power source . Electrical operation of the product ispossible as soon as one of the power supplies is available.
2
1
AUT position
priority power source
stand by power source
switching operation possibility
1
2
svrm
o_07
7_c_
1_gb
_cat
Padlocking
Up to three padlocks can be used to lockthe device.When padlocked:• manual operation is not possible• electrical controls are disabled.Padlocking in the 3 positions I, 0 and II,available in option.
atys
_008
_a_1
_cat
Backup manual operation
The product can still be switched withoutany power source using the manualoperation. The handle (supplied with theproduct) allows direct operation of thechangeover shaft. The switch cannot bemanually operated in automatic mode(AUT) or padlocked.
atys
_013
_a_1
_cat
General
• The switching operation can be driven by an external dry contact. “Pulsed contact logic” (impulse) or “maintained contact logic”(contactor), are both recognised on the control inputs.
• The type of logic must be selected during configuration (programming).• Priorities: the first order received has priority as long as it is present. A zero command has always priority, excepted in case of controls
inhibition.• ATyS 3e integrates number of operation counter and allows optional communication or inputs/outputs module connection.
Impulse logic
• The switching command is a pulsed dry contact lasting at least100 ms.
• When the order disappears, the product remains in position.Theimpulse can be of infinite duration without causing anydisturbance.
Contactor logic
• The transfer command is a maintained dry contact.• If command I or II disappears, the device returns to zero
position, if power supply is available.• A 0 command drives the device into zero position, irrespective of
the status of the I and II commands.
order I
order O
order II
position I
position O
position II
svrm
o_07
9_b_
1_gb
_cat
order I
order O
order II
position I
position O
position II
atys
_024
_a_1
_gb_
cat
Control logic�
AUT / MAN commandAn AUT / MAN selector inhibits automaticoperation and allows handle use whenpositioned in manual mode. This selectoris key type on ATyS 3e, 6e and 6m.
atys
_097
_b_1
_cat
Manual operation
�
Main accessories
�
atys
_565
_c_2
_cat
Remote control interfaceEnables operation, configuration and displayof all the functions remotely. It can beconnected to an ATyS 6e or 6m via an RJ45type link. When connected, all featuresavailable on the front of the product areinhibited. Maximum connection distance:3m. 2 modeles: ATyS D10 (visualisation) andATyS D20 (visualisation and control).
atys
_011
_a_1
_cat
Voltage sensing and power supply kitAllows voltage sensing and power supplyconnections through a controlled routing ofthe conductors, in order to avoid the use ofspecific protection devices (fuse / mcb).
A. 10
Changeover switches
The ATyS range
SOCOMEC general catalogue
Wiring diagram
�
power source
power source
1: control position 0
2: control position I
3: control position II
4: configuration of the control logic
5 : NO/NC position and pre-breaking contact for position I
6: NO/NC position and pre-breaking contact for position II
7 : Double Power Supply (accessory).
2
1
5 6
43 2 1
313 314 315 316 317
1 2
101 102
DPS7
atys
_025
_e_1
_x_c
at
power source power source 1 : control position 02 : control position I3 : control position II4 : inhibition of the control position5 : fault relays6 : auxiliary contact, closed when
the switch is padlocked
7 : auxiliary contact, closed whenthe switch is in “AUT” mode
8 : auxiliary contact, closed whenthe switch is in position 0
9 : auxiliary contact, closed whenthe switch is in position II
10 : auxiliary contact, closed whenthe switch is in position I
11 : slots for optional modules.
2
1
5
6710 9 8
2 1
13 14 24 34 43 44 53 54
6463
102
202
201
101
317
316
315
313
314
11
4
3
21
atys
_094
_d_1
_x_c
at
ATyS 6: Automatic Transfer Switches
Display + keypad• Setup and Thresholds configuration;• Timers configuration MFT (0-60 s), DTT (0-60 s), 0MF (0-20 s),
MRT (0-60 min.), 0MR (0-20 s), CDT (0- 10 min.).• Voltage, Frequency, Timers monitoring.• Test and positions control operations.
LedsPower on; Fault; Sources availability; Changeover position; AUT mode; Test and control modes of operation.
1 configurable generator set bi-stable start/stop relay(30 VDC, 5 A, AC1).1 NO fault relay activated in case of changeover positionordered and not reached (30 VDC, 5 A, AC1).
Control modes• Test on-load (load transfer): allows loss of main’s network
simulation. The complete automatic cycle is then followed.Can be activated from the keypad of the device or remotely froman external dry contact.
• Test off-load (without load transfer): allows a generator set startand stop operation.Can be activated from the keypad of the device.
• Control I, 0, II: allows the product to be driven into one of thepositions ; the automatic cycle is then no longer active.Can be activated from the keypad of the device’s front or usingand external dry contact.
• Semi automatic: when this mode is active, any transfer back tothe main network must be acknowledged on the keypad of theproduct or via an optional input contact.
• One input to control backup source changeover (when DTT timer = max value). Example: changeover operation on multiplegenerator sources after their synchronisation.
Operation�
atys
_679
_a_1
_x_c
at
General features
�
Single or three phases control on networks I and II
• Independent Under/ Over voltage and Under / Over frequencythresholds: +/- 20% of nominal value.
• Adjustable hysteresis thresholds.• Phase rotation control.
Metering• 3U on network and .• Frequency on network and .• Normal/Emergency timers.• 3I, In, P, Q, S, PF (3 phases) on ATyS 6m.
21
21
ATyS 3s ATyS 3e
�
The ATyS rangeATySATyS C30 / ATyS C40ATyS VISION softwareOther changeover switches
A. 11
Changeover switches
The ATyS range
SOCOMEC general catalogue
ATyS enclosed range
�
Product range• From 63 to 1600 A. • 230/400 VAC +/- 20%.• 3 or 4 wires applications.
Range
The ATyS 3s, 6e and 6m enclosed range offer the followingfeatures:• Non-Automatic Transfer Switch (ATyS 3s)• Automatic Transfer Switch — ATS (ATyS 6e)• Single or dual by-pass automatic transfer switch (ATyS 6m).
Features
• Compact design.• Mechanically interlocked switching.
Cable entry• Top or bottom cable entry as standard from 63 to 250 A.• Bottom cable entry as standard from 400 to 1600 A.• Specific cable entry requirements available upon request.• Neutral position located on the right as standard.• Alternative options available upon request.
Main accessories• Double (Self) power supply for ATyS 3 only.• 2nd position auxiliary contact.• Solid neutral.• 400 / 230 VAC transformers (on each network) for 3 phases
400 VAC applications.• Panel mounted ATyS D10 or D20 remote interfaces and
indication meter.
coff_
306_
a_2_
cat
Simplified wiring diagram
�
73210
209208
207206
205204
203202
20174
Pow
er 2
30 V
AC
2Pow
er 230 VAC
F1F2
13
5 6 7 8 9
1211
10
4
16
32
1
14
1
15
13 14 24 34 43 44 53 54
101
102
103
104
105
106
313
314
315
316
317
6364
RJ
Volta
ge s
ensin
gL1
L2L3
N
Voltage s
ensin
gL1
L2L3
N
17
1: control position 02: control position I3: control position II4 : remote command5: auxiliary contact, closed when the
switch is in position I6: auxiliary contact, closed when the
switch is in position II7: auxiliary contact, closed when the
switch is in position 08: auxiliary contact, closed when the
switch is in “AUT” mode9: auxiliary contact, closed when the
switch is padlocked10: gen-set start and stop command11: auxiliary power supply (for optional
modules control)12: remote “test on-load ”input13: DTT inhibit input. Transfer initiated
as soon as the input is closed whenDTT = max. value.
14: fault output15: remote control interface16: current transformers (ATyS 6m only)17: slots for optional modules.
atys
_026
_d_1
_x_c
at
Some terminal blocks are specific tothe ATyS 6m versions.
Enclosed ATS solution Enclosed dual by-pass solution
atys
_712
_a
ATyS 6e / ATyS 6m
A. 12
FunctionsATyS products are 3 and 4-pole switchesremotely controlled by volt freecontacts (ATyS 3) or automatic transferswitches (ATyS 6).They are a combination of two load-breakswitches mounted back to backelectrically and mechanically interlocked.They provide manual switching or remotecontrolled source inversion or changeoverunder load, of two low voltage powercircuits.
Conformity to standards
General characteristics• Isolation with positive break indication• On load switching• Manual emergency operation• 3 stable positions (I, 0, II) or overlapping
contacts on request (I, I+II, II) • Padlocking in 0 or in all three positions
(I, 0, II)• AUTO / MANU selector.
� The ATyS rangeATySATyS C30 / ATyS C40ATyS VISION softwareOther changeover switches
Changeover switches
ATyS63 to 3200 A
SOCOMEC general catalogue
atys
_003
_a_1
_cat
ATyS 3s
atys
_102
_a_1
_cat
ATyS 6m
• IEC 60947-3• EN 60947-3• NBN EN 60947-3• BS EN 60947-3• GB 14048
• IEC 60947-6-1• EN 60947-6-1• NBN EN 60947-6-1• BS EN 60947-6-1
ATyS M 3s
ATyS M 6e
atys
m_0
13_a
_1_c
at
atys
m_0
07_a
_1_c
at
A. 13
Changeover switches
ATyS
SOCOMEC general catalogue
1
2
3
4
5
6
7
8
9
9
10
11
12
13
atys
_615
_a_1
_x_c
atat
ysm
_032
_a_1
_x_c
at
1. Backup handle and support (included with device)
2. Handle key interlocking accessories
3. Door protective surround
4. Additional auxiliary contacts
5. Standard device
6. Connecting cable for ATyS D10 or D20remote interfaces (ATyS 6)
7. ATyS D10 or D20 interfaces (ATyS 6)
8. Plug-in optional modules (not for ATyS 3s)
9. Voltage sensing and power supply kit (ATyS 6)
10. Terminal shrouds
11. Bridging bars
12. Mounting spacers
13. Terminal screens.
Overview (for further details, please see theinstallation instructions supplied with eachdevice).
IllustrationsATyS M from 63 to 160 A
ATyS from 125 to 3200 A
1
2
3
3
4
5
11
1. ATyS D10 or D20 remote interfaces (ATyS M 6e only)
2. 1 or 2 auxiliary contacts
3. Terminal shrouds
4. Voltage sensing and power supply tap
5. Bridging bars.
A. 14
�
References
Changeover switches
ATyS63 to 3200 A
SOCOMEC general catalogue
The ATyS rangeATySATyS C30 / ATyS C40ATyS VISION softwareOther changeover switches
(1) Power-supply voltage 230 VAC.(2) 2 pieces: top and bottom.(3) 1 contact block for I, 0 and II positions.
atys
m_0
13_a
_2_c
at
�
ATyS 3ATyS M 3
pair1399 4006
63
Rating(A)
No.of poles
ATyS M3s (1)
1309 4006
1309 4016
Bridging bars
4 P 1323 4006
80 4 P 1323 4008
pair2294 4016 1309 0001
Voltage sensing and power supply tap
Terminal shrouds (2)
Auxiliary contacts (3)
100 4 P 1323 4010
125 4 P 1323 4012
160 4 P 1323 4016
atys
m_0
26_a
_1_c
at
atys
m_0
27_a
_1_c
at
atys
m_0
28_a
_1_c
at
(1) To shroud front switch top and bottom 2 references required.(2) 1 contact block for I, 0 and II positions.(3) For ATyS M 6e only.(4) For ATyS M 6s only.
atys
m_0
07_a
_2_c
at
atys
m_0
25_a
_1_c
at
�
ATyS 3ATyS M 6
pair1399 4006
63
Rating(A)
No.of poles
Network (VAC)
1309 4006
1309 4016
Bridging bars
4 P 127 / 230
4 P 230 / 400
80 4 P 127 / 230
pair2294 4016 1309 0001
Voltage sensingand powersupply tap
Terminalshrouds (1)
Auxiliarycontacts (2)
ATyS D101599 2010
ATyS D201599 2020
Remote interface (3)
1359 0000
Sealable cover (4)
ATyS M6s
1353 4006
1354 4006
1353 4008
ATyS M6e
1363 4006
1364 4006
1363 4008
4 P 230 / 400
100 4 P 127 / 230
4 P 230 / 400
1354 4008
1353 4010
1354 4010
1364 4008
1363 4010
1364 4010
125 4 P 127 / 230
4 P 230 / 400
160 4 P 127 / 230
4 P 230 / 400
1353 4012
1354 4012
1353 4016
1354 4016
1363 4012
1364 4012
1363 4016
1364 4016
atys
m_0
26_a
_1_c
at
atys
m_0
27_a
_1_c
at
atys
m_0
28_a
_1_c
at
atys
_565
_c_2
_cat
atys
m_0
43_a
atys
m_0
25_a
_1_c
at
A. 15
Changeover switches
ATyS
SOCOMEC general catalogue
(1) To shroud front switch top and bottom 2 references required. (2) To fully shroud front and rear / top and bottom 4 references required. (3) 1 set: top and bottom.(4) Available enclosed (see page A.24 “ATyS 3s in enclosure”). (5) Factory fitted.
Rating (A)
ATyS 3s
ATyS 3e
125 … 160
250 … 400
630
800 … 1800
125 … 160
250 … 400
630
800 … 1600
2000 … 3200
1599 4120
1599 4120
1599 4200 —
1599 1002
1599 1012
1599 1022
1599 1032
Plug-in optionalmodules
Auxiliarycontacts (5)
Control voltagetransformer
400/230 VAC
1599 0002
1599 0012
1599 0022
1599 0032
1599 0042
DC powersupply
1599 0004
Padlocking (5)
1509 1004
Handle key interlocking
accessories (5)
1529 0080
Door protectivesurround
—
Mountingspacers
DPS — Doublepower supply
-1599 4063
1599 4063
1599 0003 1509 1006 1529 0012 1509 00011599 4001
1509 00011539 00121509 10061599 0003
References
1599 0004 1509 1004 -1539 0080
800 3 P
4 P
1000 3 P
4 P
1523 3080
1523 4080(4)
1523 3100
1523 4100(4)
1250 3 P
4 P
1600 3 P
4 P
1523 3120
1523 4120(4)
1523 3160
1523 4160(4)
1800 3 P
4 P
1523 3180
1523 4180
1533 3080
1533 4080
1533 3100
1533 4100
1533 3120
1533 4120
1533 3160
1533 4160
—
—
2000 3 P
4 P
—
—
1533 3200
1533 4200
2500 3 P
4 P
—
—
1533 3250
1533 4250
3200 3 P
4 P
—
—
1533 3320
1533 4320
1 P
4109 0120
3 P1509 3160
4 P1509 4160
3 P1509 3200
4 P1509 4200
1 P4109 0080
1 P4109 0160
See page A.18 “Copper bars
connection kits”
3 P1509 3080
4 P1509 4080
—
Rating (A)
No.of poles
125
160
250
3 P
4 P
3 P
4 P
3 P
4 P
400 3 P
4 P
630 3 P
4 P
1523 3012
1523 4012(4)
1523 3016
1523 4016(4)
1523 3025
1523 4025(4)
1523 3040
1523 4040(4)
1523 3063
1523 4063(4)
ATyS 3s
atys
_003
_a_3
_cat
acce
s_20
5_a_
1_ca
t
acce
s_20
6_a_
1_ca
t
acce
s_20
7_a_
1_ca
t
1533 3012
1533 4012
1533 3016
1533 4016
1533 3025
1533 4025
1533 3040
1533 4040
1533 3063
1533 4063
ATyS 3e
1 P4109 0019
3 P1509 3012
4 P1509 4012
3 P2694 3014
4 P2694 4014
Bridging bars Terminal shrouds (1)(2) Terminal screens (3)
1 P4109 0025
1 P4109 0039
1 P4109 0063
3 P2694 3021
4 P2694 4021
2694 3051
2694 4051
3 P1509 3025
4 P1509 4025
1509 3063
1509 4063
�
ATyS 3ATyS 3
RS4851599 2000
2 inputs / 2 outputs
1599 2001
12 VDC1599 5012
24 VDC1599 5112
48 VDC1599 5212 —
+ OTHER ACCESSORIES
A. 16
References
�
Changeover switches
ATyS63 to 3200 A
The ATyS rangeATySATyS C30 / ATyS C40ATyS VISION softwareOther changeover switches
SOCOMEC general catalogue
800 3 P
4 P
1000 3 P
4 P
1563 3080
1563 4080(4)
1563 3100
1563 4100(4)
1250 3 P
4 P
1600 3 P
4 P
1563 3120
1563 4120(4)
1563 3160
1563 4160(4)
1573 3080
1573 4080
1573 3100
1573 4100
1573 3120
1573 4120
1573 3160
1573 4160
2000 3 P
4 P
1563 3200
1563 4200
1573 3200
1573 4200
2500 3 P
4 P
1563 3250
1563 4250
1573 3250
1573 4250
3200 3 P
4 P
1563 3320
1563 4320
1573 3320
1573 4320
1 P4109 0120
4 P1559 4080(5)
4 P1559 4081(6)
1 P4109 0160
1559 4120(5) 1559 4121(6)
1559 4160(5) 1559 4161(6)
1509 3160
1509 4160
3 P1509 3080
4 P1509 4080
Rating (A)
125 … 160
250 … 400
630
800 … 1600
2000 … 3200
Plug-in optionalmodules
Remote control
interface
RJ45 connecting
cable
1599 0002
1599 0012
1599 0022
1599 0032
1599 0042
Auxiliarycontacts (7)
1599 4120
1599 4200 —
Control voltagetransformer400/230 VAC Padlocking (7)
Handle key interlocking
accessories (7)
Door protectivesurround
Mountingspacers
4 P1559 4200(5)
4 P1559 4201(6)
(1) To shroud front switch top and bottom 2 references required. (2) To fully shroud front and rear / top and bottom 4 references required. (3) 1 set: top and bottom.(4) Available enclosed (see page A.25 “ATyS 6e in enclosure”). (5) Neutral on the right. (6) Neutral on the left. (7) Factory fitted.
1 P4109 0080
DC power supply
3 P1509 3200
4 P1509 4200
1509 00011539 00121509 10061599 00031599 4063
Rating (A)
No.of poles
125
160
250
3 P
4 P
3 P
4 P
3 P
4 P
400 3 P
4 P
630 3 P
4 P
1563 3012
1563 4012(4)
1563 3016
1563 4016(4)
1563 3025
1563 4025(4)
1563 3040
1563 4040(4)
1563 3063
1563 4063(4)
ATyS 6e
atys
_097
_b_2
_cat
1573 3012
1573 4012
1573 3016
1573 4016
1573 3025
1573 4025
1573 3040
1573 4040
1573 3063
1573 4063
ATyS 6m
4 P1559 4012(5)
4 P1559 4013(6)
Bridging bars Voltage sensing kit
1 P4109 0025
1 P4109 0039
1 P4109 0063
1559 4025(5) 1559 4026(6)
�
Commutateur VM1 I-0-IIATyS 6
1559 4040(5) 1559 4041(6)
1559 4063(5) 1559 4064(6)
3 P2694 3014
4 P2694 4014
Terminal shrouds (1)(2)
3 P2694 3021
4 P2694 4021
2694 3051
2694 4051
3 P1509 3012
4 P1509 4012
Terminal screens (3)
3 P1509 3025
4 P1509 4025
1509 3063
1509 4063
3 P1559 3012
1559 3025
1559 3040
1559 3063
1 P4109 0019
acce
s_20
5_a_
1_ca
t
acce
s_60
6_a_
1_ca
t
acce
s_20
6_a_
1_ca
t
acce
s_20
7_a_
1_ca
t
3 P1559 3200
1559 3160
1559 3120
3 P1559 3080
See page A.18 “Copper bars
connection kits”
—
12 VDC1599 5012
24 VDC1599 5112
48 VDC1599 5212
1599 0004 1509 1004 1539 0080 —
1599 2009
ATyS D101599 2010
ATyS D201599 2020
RS4851599 2000
2 inputs / 2 outputs
1599 2001
+ OTHER ACCESSORIES
A. 17
ATyS M — Accessories
Changeover switches
ATyS
SOCOMEC general catalogue
Bridging bars
atys
m_0
25_a
_1_c
at
ReferencesRating (A) No. of poles Reference
63 … 125160
44
1309 40061309 4016
UseTo provide common point oneither incoming or outgoingterminals.
Voltage sensing and power supply tapReferenceUse
Allows up to 2 x <=1.5 mm2
voltage sensing or power cablesconnection. To be mounted inany terminal cage when bridgingbar not used.
Rating (A) Reference
63 … 160
No. of parts
Pair 1399 4006 (1)
atys
m_0
26_a
_1_c
at
Rating (A) Reference
63 … 160 2294 4016 (1)
Terminal shrouds
atys
m_0
27_a
_1_c
at
ReferenceNo. of parts Position
Pair Top and bottom
UseProtection against directcontact with the connectionterminals or parts.AdvantagesPerforations enabling remotethermographic inspectionwithout dismantling.
Auxiliary contacts
atys
m_0
28_a
_1_c
at
ReferenceUseUp to 2 auxiliary contactsaccessory per product.Each accessory integrates 3NOC auxiliary contacts, one perposition I, 0, II.Characteristics: 250 VAC / 5 Amaximum.
Rating (A) Reference
63 … 160 1309 0001
Reference
1359 0000
Sealable coverReferenceRating (A)
63 … 160
UseControls settings cover toprevent ATyS M 6s parametersaccess due to a sealable facility.
atys
m_0
43_a
(1) 2 parts per reference.
(1) To shroud front switches top and bottom 2 references required.
A. 18
�
Changeover switches
ATyS63 to 3200 A
The ATyS rangeATySATyS C30 / ATyS C40ATyS VISION softwareOther changeover switches
SOCOMEC general catalogue
ATyS — Accessories
Bridging bars
acce
s_20
5_a_
1_ca
tac
ces_
041_
a_1_
cat
ReferencesRating (A) No. of poles Section (mm) Reference
125 … 160 1 20 x 2.5 4109 0019250 1 25 x 2.5 4109 0025400 1 32 x 5 4109 0039630 1 50 x 5 4109 0063800 … 1000 1 50 x 6 4109 00801250 1 60 x 8 4109 01201600 … 1800 1 90 x 10 4109 0160
UseTo provide common point oneither incoming or outgoingterminals.
Copper bars connection kits
Fig.1
2
1
acce
s_22
6_a_
1_x_
cat
Fig.2
4
1
3
acce
s_22
8_a_
1_x_
cat
Fig.3
5
1
3
2
acce
s_23
0_a_
1_x_
cat
ReferencesTop or bottom flat connection — Fig. 1
Rating (A) Reference
2000 … 2500
32003200
2699 1200
standard2699 1200
Part
Bolt set — part 2
Bolt set — part 2
Qty to order per pole (1)
2
/2
UseTo allow:- connection between the two
power terminals from a samepole for 2000 to 3200 A ratings(Fig. 1 and Fig 2)
— top or bottom bridgingconnection (Fig. 3).
For 3200 A rating, the twopower terminals are deliveredbridged from factory.Bolt sets must be orderedseparately.
DimensionsSee page A.35, for connectionkit assembly.
Technical notice for thesespecific accessories isdownloadable fromwww.socomec.com.
2000 … 2500 2619 12002
Top or bottom edgewise connection — Fig. 2
Rating (A) Reference
2000 … 2500
3200
3200
2639 1200 (2)
standard
2639 1200 (2)
Part
Right angle — part 4
Right angle — part 4
Qty to order per pole (1)
2
/
23200 2629 1200 (2)T piece — part 3 2
2000 … 2500 2619 120022000 … 2500 T piece — part 3 2 2629 1200 (2)
Top or bottom bridging connection — Fig. 3
Rating (A) Reference
2000 … 2500
3200
3200
4109 0250 (2)
standard
4109 0320 (2)
Part
Bar — part 5
Bar — part 5
Qty to order per pole (1)
1
/
13200 2699 1200Bolt set — part 2 2
3200 2629 1200 (2)T piece — part 3 1
2000 … 2500 2619 120022000 … 2500 Bolt set — part 2 2
2000 … 2500 2629 1200 (2)T piece — part 3 1
(1) Example for 3-pole device: order 3 times the quantities.(2) Bolt set is provided with the accessories.
2699 1200
Connection — part 1
Connection — part 1
Connection — part 1
Connection — part 1
Connection — part 1
Connection — part 1
A. 19
Changeover switches
ATyS
SOCOMEC general catalogue
ATyS — Accessories
Voltage sensing and power supply kit
atys
_606
_aat
ys_6
03_a
ReferencesFor ATyS 6 — 3 pole
Rating (A) Reference
125 … 160 1559 3012250 1559 3025400 1559 3040630 1559 3063800 … 1000 1559 30801250 1559 31201600 1559 31602000 … 3200 1559 3200
For ATyS 6 — 4 pole
Rating (A)
Neutral on the right Neutral on the left
Reference Reference
125 … 160 1559 4012 1559 4013
1250 1559 4120 1559 41211600 1559 4160 1559 4161
250 1559 4025 1559 4026400 1559 4040 1559 4041630 1559 4063 1559 4064800 … 1000 1559 4080 1559 4081
2000 … 3200 1559 4200 1559 4201
UseFor ATyS 6 power supply andvoltage measurement (4 wires,three phases).Routing of the conductors is controlled, which means thatno specific protective device is necessary for theseconnections.The kit can be fitted on the topor the bottom of the switch.NB: the 3-pole version does notintegrate the power supply.
From 125 to 630 A.
From 800 to 3200 A.
Plug-in optional modules
atys
_016
_a_1
_cat
ReferencesDescription of accessories Reference
COM RS485 (No. 1) 1599 20002 inputs/2 outputs (No. 2) 1599 2001
UseNo. 1: COM module control andstate feedback of the changeoverswitch via a 2 or 3-wire RS485link with JBUS/MODBUSprotocol® and transmissionspeed up to 38,400 baud.No. 2: module with 2 inputs/2 outputs• For ATyS 3e:
2 inputs: changeover control +backup network availability ; 2 outputs: a load shedderrelay + fault relay.
• For ATyS 6e and 6m: 2 inputs/2 outputs, programmable.
Terminal shrouds
acce
s_20
6_a_
1_ca
t
References
Rating (A) No. ofpoles Position Reference
125 … 160 3 top / bottom / front (I) / rear (II) 2694 3014(1)(2)
125 … 160 4 top / bottom / front (I) / rear (II) 2694 4014(1)(2)
250 … 400 3 top / bottom / front (I) / rear (II) 2694 3021(1)(2)
250 … 400 4 top / bottom / front (I) / rear (II) 2694 4021(1)(2)
630 3 top / bottom / front (I) / rear (II) 2694 3051(1)(2)
630 4 top / bottom / front (I) / rear (II) 2694 4051(1)(2)
(1) To shroud front switch top and bottom 2 references required.(2) To fully shroud front and rear / top and bottom 4 references required.
UseProtection against directcontact with the connectionterminals or parts.AdvantagesPerforations enabling remotethermographic inspectionwithout dismantling.
A. 20
�
Changeover switches
ATyS63 to 3200 A
The ATyS rangeATySATyS C30 / ATyS C40ATyS VISION softwareOther changeover switches
SOCOMEC general catalogue
ATyS — Accessories
Control voltage transformer
ReferencesRating (A) Reference
125 … 630 1599 4063800 … 18002000 … 3200
1599 41201599 4200
UseEnables a 230 VAC device to besupplied with 400 VAC.
Auxiliary contacts
acce
s_06
5_a_
1_ca
t
ReferencesFor ATyS 3s
Rating (A) Reference
125 … 160 1599 1002250 … 400 1599 1012630 1599 1022800 … 1800 1599 1032
For ATyS 3e, 6e and 6m
Rating (A) Reference
125 … 160 1599 0002250 … 400 1599 0012630 1599 0022800 … 1600 1599 00322000 … 3200 1599 0042
UsePre-breaking and signalling of positions I and II: 1 extra NO / NC auxiliarycontact in each position (factory fitted).
Low level AC: please consult us.
Terminal screens
acce
s_20
7_a_
1_ca
t
References
Rating (A) No. of poles Position Reference
125 … 160 3 top / bottom 1509 3012125 … 160 4 top / bottom 1509 4012250 … 400 3 top / bottom 1509 3025250 … 400 4 top / bottom 1509 4025630 3 top / bottom 1509 3063630 4 top / bottom 1509 4063800 … 1250 3 top / bottom 1509 3080800 … 1250 4 top / bottom 1509 40801600 … 1800 3 top / bottom 1509 31601600 … 1800 4 top / bottom 1509 41602000 … 3200 3 top / bottom 1509 32002000 … 3200 4 top / bottom 1509 4200
UseIncoming and outgoingprotection against directcontacts with the connectionterminals or parts.
Inter phase barriers
acce
s_03
6_a_
1_ca
t
References
Rating (A) No. of poles Reference
125 … 160 3 2998 0033
125 … 160 4 2998 0034
250 … 400 3 2998 0023
250 … 400 4 2998 0024
630 3 2998 0013
630 4 2998 0014
800 … 3200 3 / 4 standard
UseSafety isolating separationbetween the terminals, essentialfor use at 690 VAC or in a dustyatmosphere.The terminal shrouds alsoprovide phase separation forATyS from 125 to 630 A.
A. 21
Changeover switches
ATyS
SOCOMEC general catalogue
ATyS — Accessories
Padlocking in the 3 positions I-0-II
Aty
s_12
5_a_
1_ca
t
ReferencesRating (A) Reference
125 … 630 1599 0003800 … 3200 1599 0004
UseAllows locking of the operationin the 3 positions I, 0 and II. Factory fitted.
DC power supplyReferences
Rating (A) Voltage Reference
125 … 1800 1599 5012125 … 1800 1599 5112125 … 1800 1599 5212
UseAllows standard ATyS, to be DCpower supplied.To be positioned as close aspossible from DC power supplysource.Not available for ratings from2000 A to 3200 A.
12 VDC / 230 VAC24 VDC / 230 VAC48 VDC / 230 VAC
Mounting spacers
atys
_009
_a_1
_cat
ReferenceRating (A) Description of accessories Reference
125 … 630 1 set of 2 spacers 1509 0001
UseRaises the device’s terminals 10 mm away from the bottom of the enclosure or frame onwhich the device is mounted.This may also be used toreplace the original mountingspacers.
Handle key interlocking accessories
Aty
s_10
1_a_
1_ca
t
ReferencesRating (A) Reference
125 … 630 1509 1006800 … 3200 1509 1004
UseLocking the electrical controland the backup control inposition 0 using a RONISEL11AP lock.Factory fitted.As standard, locking in position 0.Optional padlocking in 3positions: 0, I and II.
Door protective surround
atys
_595
_a_1
_cat
ReferencesFor ATyS 3s
Rating (A) Reference
125 … 630 1529 0012800 … 1800 1529 0080
For ATyS 3e, 6e and 6m
Rating (A) Reference
125 … 630 1539 0012800 … 3200 1539 0080
UseDoor finishing surround forprotecting ATyS application.
A. 22
�
Changeover switches
ATyS63 to 3200 A
The ATyS rangeATySATyS C30 / ATyS C40ATyS VISION softwareOther changeover switches
SOCOMEC general catalogue
ATyS — Accessories
Remote interfaces for ATyS M 6e and ATyS 6e, 6m, C30
atys
_564
_c_1
_cat
atys
_565
_c_1
_cat
Reference
Description of accessories Reference
ATyS D10 interfaceATyS D20 interface
1599 20101599 2020
UseDedicated to applications wherethe ATyS is back panelmounted.Interfaces are self powered fromthe ATyS. Maximum connection distance:3 m.
ATyS D10To display source availabilityand changeover state on thecabinet front panel.
ATyS D20In addition to the ATyS D10allows displays, operation andconfiguration on the cabinetfront panel.
Door mounting2 holes Ø 22.5.Master ATyS connection viaRJ45 cable, not isolated.
Drilled holes.
atys
_597
_a
Ø 22.5
4036
20
= =
96 x 96
atys
_161
_a_1
_x_c
at
RJ45 link for ATyS connection.
A. 23
Changeover switches
ATyS
SOCOMEC general catalogue
ATyS — Accessories
Double power supply — DPSReference
Description of accessories Reference
Double Power Supply (DPS) 1599 4001
Input 1 Output
230 VAC 230 VAC (Input 1)
Input 2
0 VAC0 VAC 230 VAC (Input 2)230 VAC
230 VAC 230 VAC (Input 1)230 VAC0 VAC 0 VAC0 VAC
UseAllows an ATyS 3s to be suppliedby two 230 VAC 50/60 Hznetworks.
Inputs- The input is considered as
“active” from 200 VAC- Max. voltage: 280 VAC- Internal protection: each input
is fuse protected- Connection on terminals:
max. 6 mm2
— Modular device: 4 moduleswidth.
atys
_612
_a_2
_cat
3
21
atys
_616
_a
1 and 2. Voltage inputs.
3. Voltage output.
For ATyS
Connecting cable for remote interfaces D10 / D20UseConnection between interface(type D10 or D20) and ATyS M 6e or ATyS 6e, 6m, C30.Characteristics: RJ45 8 wiresnot insulated straightconnection, 3 meters length.
atys
_209
_a_1
_cat
Type Reference
RJ45 cable
Length
3 m 1599 2009
ReferenceFor ATyS M 6e and ATyS 6e, 6m, C30
A. 24
�
Changeover switches
ATyS63 to 3200 A
The ATyS rangeATySATyS C30 / ATyS C40ATyS VISION softwareOther changeover switches
SOCOMEC general catalogue
Enclosed ATyS 3s
Steel enclosure
Functions• Non-Automatic Transfer Switch• Compact design• Mechanically interlocked switching• Connection ready for external logic control.
Conformity to standards• IEC 60439-1
General characteristics• Adapted to mechanical risk and dust hazard• Protection degree: IP54 (standard device)• Colour: RAL 7035• Cable gland plate: top and bottom from 63 to 250 A,
bottom from 400 to 1600 A• Material: steel thickness 2 mm• Coating: epoxy polyester powder• Wall mounting: 4 wall mounting brackets supplied — not mounted
(rating ≤ 400 A), floor standing feet (rating > 630 A)• Door: solid with hinges• Locking system: 3 mm double-bar key (key supplied)• Miscellaneous: 2 earth connection points, neutral on the right.• Accessories: double power supply, 2nd auxiliary contact, solid
neutral, 400/230 VAC transformers (on each network), 3 positionspadlocking, …
Available on request• Enclosures and specific connections: neutral on the left, …
Rating (A) Reference
Dimensions
coff_
305_
a_1_
cat
Standard device — 230 VAC
WM
H N
223
12.5
D
10.5Z1Z2
3
1
2atys
_619
_d_1
_gb_
cat
(1) Wall mounting brackets delivered up to 400 A.(2) Floor standing feet from 630 A (add 200 mm for feet, at H dimension).(3) Mounting spacers.
Rating (A)
Max. connectionsection (mm2)
Weight(kg)
50 —
160 95 25250 150 45400 240 50630 2 x 240 70800 2 x 300 1351000 2×300 / 4×240 1401250 2×300 / 4×240 2701600 6×185 / 4×300 375
Z2
—
134134.5134.5190
253.5253.5253.5253.5
Z1
—
3839.539.553
66.566.566.567.5
N
608
608958958
——
M
448
448698698
——
D
300
300475475475660660830830
W
400
40065065065080080010001000
H
650
6501000100010001200120016001600
Connectionsection(mm2)
—
70120240
2 x 1852 x 2404 x 1504 x 1854 x 240
125 50 2513438608448300400650-
63 1723 4006
160 1723 4016250 1723 4025400 1723 4040630 1723 4063800 1723 40801000 1723 41001250 1723 41201600 1723 4160
No. of poles
4
44444444
100 1723 40104125 1723 40124
Solid neutral Reference
Customer fitted accessories
63 … 160 A 1599 1006250 A 1599 1025400 A 1599 1040630 A 1599 1063800 A 1599 10801000 A 1599 11001250 A 1599 11201600 A 1599 1160
Description Reference
Factory fitted accessories
Double power supply 1599 90012nd auxiliary contact: from 63 to 630 A 1599 90022nd auxiliary contact: from 800 to 1600 A 1599 9012400 / 230 VAC transformer3 positions padlocking 1599 9003
consult us
63 … 100
A. 25
Changeover switches
ATyS
SOCOMEC general catalogue
Enclosed ATyS 6e
Steel enclosure
Functions• Automatic Transfer Switch — ATS• Compact design• Mechanically interlocked switching• Connection ready for external logic control.
Conformity to standards• IEC 60947-6-1• IEC 60439-1
General characteristics• Adapted to mechanical risk and dust hazard• Protection degree: IP54 (standard device)• Colour: RAL 7035• Cable gland plate: top and bottom from 63 to 250 A,
bottom from 400 to 1600 A• Material: steel thickness 2 mm• Coating: epoxy polyester powder• Wall mounting: 4 wall mounting brackets supplied — not mounted
(rating ≤ 400 A), floor standing feet (rating > 630 A)• Door: solid with hinges• Locking system: 3 mm double-bar key (key supplied)• Miscellaneous: 2 earth connection points, neutral on the right.• Accessories: 2nd auxiliary contact, solid neutral, 400/230 VAC
transformers (on each network), 3 positions padlocking, …
Available on request• Enclosures and specific connections: neutral on the left, …
coff_
306_
a_1_
cat
Reference
Customer fitted accessories
1599 20101599 20201599 20091599 20001599 2001
—
Description
ATyS D10ATyS D20RJ45 connection cable (1)
Communication RS485 MODBUS2 inputs / 2 outputsSolid neutral (see page A.24 “ATyS 3s in enclosure”)
Rating (A) Reference
Dimensions
Standard device — 230 VAC
WM
H N
12.5
D
280
Z1Z2
3
1
2atys
_621
_c_1
_gb_
cat
(1) Wall mounting brackets delivered up to 400 A.(2) Floor standing feet from 630 A (add 200 mm for feet, at H dimension).(3) ATyS D10 or D20 interfaces.
(1) “RJ45 connection” cable is required.
Rating (A)
Max. connectionsection (mm2)
Weight(kg)
50 —
160 95 25250 150 45400 240 50630 2 x 240 70800 2 x 300 1351000 2×300 / 4×240 1401250 2×300 / 4×240 2701600 6×185 / 4×300 375
Z2
—
134134.5134.5190
253.5253.5253.5253.5
Z1
—
3839.539.553
66.566.566.567.5
N
608
608958958
——
M
448
448698698
——
D
300
300475475475660660830830
W
400
40065065065080080010001000
H
650
6501000100010001200120016001600
Connectionsection(mm2)
—
70120240
2 x 1852 x 2404 x 1504 x 1854 x 240
125 50 2513438608448300400650-
63 1763 4006
160 1763 4016250 1763 4025400 1763 4040630 1763 4063800 1763 40801000 1763 41001250 1763 41201600 1763 4160
No. of poles
4
44444444
100 1763 40104125 1763 40124
Description Reference
Factory fitted accessories
2nd auxiliary contact: from 63 to 630 A 1599 90222nd auxiliary contact: from 800 to 1600 A 1599 9032400 / 230 VAC transformer3 positions padlocking 1599 9003
consult us
63 … 100
A. 26
�
Changeover switches
ATyS63 to 3200 A
The ATyS rangeATySATyS C30 / ATyS C40ATyS VISION softwareOther changeover switches
Enclosed ATyS 6 with isolation by-pass
SOCOMEC general catalogue
Functions• ATyS 6m Automatic Transfer Switch provides all functions
required for break before make ATS applications• The SOCOMEC by-pass system allows complete ATS isolation.
Top and bottom isolation is achieved using the SOCOMEC 12+4 pole by-pass switch up to 630 A
• For the double line version during the ATS isolation, supply,selection remains possible thanks to a manual changeover
• ATyS 6m associated to a ATyS D20 remote display allowsconfiguration, operation and measurement from outside the panel(adjustable time/transfer delays and control level (U,F), generatorstart/stop control,…)
• Different optional accessories are available.
Conformity to standards• IEC 60947-6-1• IEC 60439-1• IEC 60529
General characteristics
Product range• From 63 to 1600 A, 4 pole, 3 or 4 wires applications • 400/230 VAC +/- 20%, 50/60 Hz; self supplied from incoming
sources
Main features• ATS logic control sequence (dual source automatic changeover)• 3 phases voltage and frequency detection & phase rotation
control of both sources• Generator start / stop relay output• ATS I, 0, II electrical control by volt free dry contacts• ATS Emergency manual operation• ATS position 0 • Isolation by-pass and manual changeover 0, I, II auxiliary contacts• ATS Auto / Manual key selector with auxiliary contact.
Enclosure• IP 41 protection rating as standard• Hinged door, double bar locking system• Wall mounting brackets delivered up to 400 A • Floor standing feet from 630 to 1600 A rating• Terminals protection screen• Steel enclosure• RAL 7035.
Cable entry• Bottom cable entry as standard• Specific cable entry requirements available upon request• Neutral position located on the right as standard• Alternative options available upon request.
Rating (A) Reference
atys
_712
_a_1
_cat
Standard device — 230 VAC
63 1774 4007
125 1774 4013160 1774 4016250 1774 4025400 1774 4040630 1774 4063800 1774 4080
1250 1774 41201600 1774 4160
No. of poles
4
444444
44
100 1774 4011
Reference
1773 4007
1773 40131773 40161773 40251773 40401773 40631773 4080
1773 41201773 4160
1000 1774 41004 1773 4100
1773 40114
Description Reference
Customer fitted accessories
Communication RS485 MODBUS 1599 20002 inputs / 2 outputs 1599 2001Solid neutral consult us
Description Reference
Factory fitted accessories
2nd auxiliary contact (1 per position) 1599 9022400 / 230 VAC transformer (1 per network) consult us3 positions padlocking 1599 9003Clock exerciser with dataloging3 current transformers (CTs) consult us
consult us
Steel enclosure
Single line
Double line
atys
_717
_a_1
_gb_
cat
atys
_718
_a_1
_gb_
cat
SIRCOVER by-passATS 12 + 4
Up to 400 A
From to 630 A LOAD Earth connectionCu 15 x 3
SIRCOVER
ATyS 6m
optional control
1-2 2-2 1-2
By-pass ATSQ3
Q1
Q2
N
133.1
207.
6
Grand plate
Example: ATyS 6m 400 A — double line version with isolation by-pass inenclosure.
A. 27
Changeover switches
ATyS
SOCOMEC general catalogue
Illustrations
Operation
• ATS position:
— I1, I2, I3: closed
— II: opened
• By-pass position:
— I1, I2, I3: opened
— II: closed
For the double line version, I4 or II2 closed depending on supply source required.
Enclosed ATyS 6 with isolation by-pass (continued)
Steel enclosure
atys
_713
_a_1
_gb_
cat
T1 T2
III3
I2I1
ATyS 6m
Load
By-pass ATS
ATS By-pass
ATyS from 125 to 630 A — SINGLE LINEat
ys_7
14_a
_1_g
b_ca
t
T1 T2
S2
I4
III3
I2I1
S1
ATyS 6m
Load
By-pass ATS
SIRCOVER
ATS By-pass
III
0
II2
ATyS from 125 to 630 A — DOUBLE LINE
atys
_715
_a_1
_gb_
cat
T1 T2
III3
I2I1
ATyS 6m
Load
SIRCOVER
ATS By-pass
SIRCO
ATS By-pass
ATyS from 800 to 1600 A — SINGLE LINE
atys
_716
_a_1
_gb_
cat
T1 T2
I4
III3
I2I1
ATyS 6m
Load
SIRCOVER
SIRCOVERATS By-pass
III
0
II2
SIRCO
ATS By-pass
ATyS from 800 to 1600 A — DOUBLE LINE
• 1 ATyS 6m
• 1 SIRCOVER 12 + 4 poles• 1 ATyS 6m
• 1 SIRCOVER 12 + 4 poles
• 1 SIRCOVER 4 poles
• 1 ATyS 6m
• 1 SIRCO 8 poles and 1 SIRCOVER 4 poles
• 1 ATyS 6m
• 1 SIRCO 8 poles and 1 SIRCOVER 4 poles
• 1 SIRCOVER 4 poles
A. 28
�
Changeover switches
ATyS63 to 3200 A
The ATyS rangeATySATyS C30 / ATyS C40ATyS VISION softwareOther changeover switches
Enclosed ATyS 6 with isolation by-pass (continued)
SOCOMEC general catalogue
Rating (A) H W
63 1000 1000
160 1000 1000250 1200 1200400 1200 1200
D
400
400400400
Connectionsection (mm2)
—
70120240
Max. connection section (mm2)
50
95150240
Wall mounting — Bottom
1. Remote interface ATyS D202. Up to 400 A3. From 630 A
100 1000 1000 400- 50125 1000 1000 400- 50
Rating (A) H W
630 1600 1200
1250 2200 16001600 2200 1600
D
550
10001000
Connectionsection (mm2)
2 x 150
—
Max. connection section (mm2)
2 x 300
4 x 1854 x 400
Floor standing — Bottom
800 2200 1400 8002 x 185 2 x 3001000 2200 1400 10002 x 240 2 x 400
W
H
D
1
212.5
3
M
N
Dimensions
atys
_708
_a_1
_gb_
cat
Double line version
Rating (A) H W
63 1000 800
160 1000 800250 1200 800400 1200 800
D
400
400400400
Connectionsection (mm2)
—
70120240
Max. connection section (mm2)
50
95150240
Wall mounting — Bottom
100 1000 800 400- 50125 1000 800 400
M
848
848848848
848848
N
958
95811581158
958958- 50
Rating (A) H W
630 1600 1000
1250 2200 10001600 2200 1000
D
400
10001000
Connectionsection (mm2)
300
—
Max. connection section (mm2)
300
4 x 1854 x 400
Floor standing — Bottom
800 2200 1000 10002 x 185 2 x 3001000 2200 1000 10002 x 240 2 x 400
Single line version
Steel enclosure
M
—
—
N
—
—
— — —
M
1048
104812481248
N
958
95811581158
1048 9581048 958
M
—
—
N
—
—
— — —
A. 29
Changeover switches
ATyS
SOCOMEC general catalogue
Functional diagram
Priority sourceBackup source
1: position 0 control2: position I control3: position II control4: position control inhibition inputs (0-I-II)5: auxiliary contact, closed when the switch is in position I6: auxiliary contact, closed when the switch is in position II7: auxiliary contact, closed when the switch is in position 08: auxiliary contact, closed when the switch is on “AUT” mode9: auxiliary contact, closed when the switch is padlocked10: gen-set start command11: auxiliary power supply (for optional modules control)12: remote “test on-load ”input
13: DTT inhibit input. Transfer initiated as soon as the input is closed whenDTT = max. value.
14: fault output15: remote control interface16: slots for optional modules17: 3 current transformers (Cts) for ATyS metering18: by-pass position19: ATS position20: Priority source used21: Backup source used101 — 102: supply 220 -20% / 240 +20%201 — 202: supply 220 -20% / 240 +20%2
1
2
1
2
1
73210
209208
207206
205204
203202
20174
Pow
er 2
30 V
AC
2Pow
er 230 VAC
13
5 6 7 8 9
1211
10
43
21
14
1
15
13 14 24 34 43 44 53 54
101
102
103
104
105
106
313
314
315
316
317
6364
RJ
L1L2
L3N L1
L2L3
N
16
13 14 24 34 43 44 53 54
313
314
315
316
317
6364
RJ
73210
209208
20774
12
Load
ATyS6m
17
Voltage sensing
Volta
ge s
ensi
ng
21
35
46
87
911
1012
18
19
20
21
Manual changeover(only for the double line)A
Isolationby-pass
B+C SIRCOVER 12+4p (from 63A to 630A)
B SIRCOVER 8p (from 800A to 1600A)
C SIRCOVER 4p (from 800A to 1600A)
C C
A
B
A
B
atys
_719
_a_1
_gb_
cat
Environment
• Operating temperature: -10 to +40 °C without de-rating.
• Operating temperature: +40 to +65 °C with de-rating.
• Maximum storage is one year.
• 80 % humidity non condensing at +55 °C.
• 95 % humidity non condensing at +40 °C.
• Maximum operating altitude without switch de-rating is 2000 mabove sea level.
The complete enclosure meets the following environmental requirements:
Enclosed ATyS 6 with isolation by-pass (continued)
Steel enclosure
A. 30
ATyS M — Characteristics (according to IEC 60947)
80 A 100 A 125 A
Rated operational currents Ie (A)
Rated voltageAccording to IEC 60947-3
Load duty category A/B(1) A/B(1) A/B(1)
415 VAC AC-21 A / AC-21 B
(1) A/B: Category with index A = frequent operation / Category with index B = infrequent operation.(2) With terminal shrouds or phase barrier.(3) For a rated operating voltage Ue = 400 VAC.(4) Between the order given and the arrival in position (under the nominal conditions).
Thermal current Ith (40°C)
Rated insulation voltage Ui (V) (power circuit)Rated impulse withstand voltage Uimp (kV) (power circuit)
Overload capacityRated short-time withstand current 1 s. Icw (kA rms) Short-circuit making capacity (kA peak)(3)
ConnectionMinimum Cu cable section (mm2) Maximum Cu cable section (mm2) Tightening torque min / max (Nm)
Switching time (nominal voltage)I — 0 or II — 0 (ms)(4)
I — II or II — I (ms)(4)
Power-supply toleranceSupply 230 VAC min / max (VAC)
Control supply power demandMax current under 230 VAC (A)
Mechanical characteristicsEndurance (number of operating cycles)Weight switch (kg)
80/80 100/100 125/125
A/B(1)
160/160AC-22 A / AC-22 B 80/80 100/100 125/125 160/160AC-23 A / AC-23 B 80/80 100/100 125/125 125/160
A/B(1)
63/6363/6363/63
800 800 8006 6 6
63 A8006
160 A8006
Rated insulation voltage Ui (V) (operation circuit)Rated impulse withstand voltage Uimp (kV) (operation circuit)
300 300 3004 4 4
3004
3004
4 4 417 17 17
417
417
Prospective short-circuit current (kA rms)(3) 50 50 5050 50Associated fuse rated (A)(3) 80 100 12563 160
6 6 6 670 70 70 704/6 4/6 4/6 4/6
6704/6
50 50 50 50180 180 180 180
50180
Duration of “electrical blackout” I — II (ms) minimum (ATyS M 3s)Duration of “electrical blackout” I — II (ms) minimum (ATyS M 6s or 6e)
60 60 60 6090 90 90 90
6090
176/288 176/288 176/288 176/288 176/288
30 30 30 30 30Nominal power (VA) 6 6 6 6 6
10 000 10 000 10 000 10 0003.5 3.5 3.5 3.5
10 0003.5
690 VAC(2) AC-21 A / AC-21 B 80/80 100/100 125/125 160/160AC-22 A / AC-22 B 80/80 80/80 100/125 100/125AC-23 A / AC-23 B 63/63 80/80 80/80 80/80
63/6363/6363/63
415 VAC AC-31 A / AC-31 B 80/80 100/100 100/125 100/160AC-32 A / AC-32 B 80/80 100/100 100/125 100/160AC-33 A / AC-33 B -/80 -/80 -/80 -/80
63/6363/63-/63
According to IEC 60947-6-1
�
Changeover switches
ATyS63 to 3200 A
The ATyS rangeATySATyS C30 / ATyS C40ATyS VISION softwareOther changeover switches
SOCOMEC general catalogue
A. 31
Changeover switches
ATyS
SOCOMEC general catalogue
ATyS — Characteristics (according to IEC 60947)
400 A 630 A 800 A
Rated operational currents Ie (A)
Rated voltageAccording to IEC 60947-3
Load duty category A/B(1) A/B(1) A/B(1)
(1) A/B: Category with index A = frequent operation / Category with index B = infrequent operation. (2) With terminal shrouds or phase barrier. (3) 3-poledevice with 2 pole in series for the + and 1 pole for the -. (4) 4-pole device with 2 pole in series by polarity. (5) For a rated operating voltage Ue = 400 VAC.(6) Between the order given and the arrival in position (under the nominal conditions).
Thermal current Ith (40°C)
Rated insulation voltage Ui (V) Rated impulse withstand voltage Uimp (kV)
Overload capacityRated short-time withstand current 1 s. Icw (kA rms) Rated peak withstand curent (kA peak)(5)
ConnectionMinimum Cu cable section (mm2)
Maximum Cu cable section (mm2) Maximum Cu busbar width (mm)
Switching timeI — II or II — I (s)(6)
I — O or II — O (s)(6)
Power-supply toleranceSupply 230 VAC min / max (VAC)
Control supply power demandSupply 230 VAC inrush / nominal (VA)
Mechanical characteristicsEndurance (number of operating cycles)Weight of 3 p switch (ATyS 3) (kg) Weight of 4 p switch (ATyS 3) (kg)
A/B(1)A/B(1)
800 1000 10008 12 12
250 A8008
160 A8008
125 A8008
1000 A100012
9 13 2630 45 55
930
3580
Prospective short-circuit current (kA rms)(5) 18 70 5050 100Associated fuse rated (A)(5) 400 630 800250
720100160
720100125 1000
95 185 2 x 150 2 x 185
150 240 2 x 300 2 x 30032 32 50 63
50
9525
35
5025
2 x 240
4 x 185Minimum Cu busbar section (mm2) — — 2 x 30 x 5 2 x 40 x 5— 2 x 50 x 5
63Tightening torque min / max (Nm) 20/26 20/26 20/26 -9/139/13 —
1.3 1.3 1.3 2.60.85 0.85 0.85 1.6
0.750.45
0.750.45
2.61.6
176/288176/288176/288 176/288 176/288 176/288 176/288
420/100420/80420/80 420/100 420/110 450/120 450/120
8 000 8 000 5 000 4 0003.73.8
4.75.2
5.25.7
19.623.1
10 0003.33.4
10 0003.23.3
4 00023.124.6
A/B(1)A/B(1)
415 VAC AC-31 B 400 630 800 1000250160125
According to IEC 60947-6-1
Weight of 3 p switch (ATyS 6) (kg) 4.5 5.5 6 20.44.14 23.9Weight of 4 p switch (ATyS 6) (kg) 4.6 6 6.5 23.94.24.1 25.4
Duration of “electrical blackout” I — II (s) 0.6 0.6 0.6 1.50.30.3 1.5
125/125 160/160 250/250 400/400125/125 160/160 250/250 400/400125/125 160/160 250/250 250/250125/125 160/160 250/250 400/400125/125 160/160 200/250 200/250125/125 125/125 125/160 125/16063/80 63/80 100/125 100/125
125/125 160/160 250/250 400/400125/125 160/160 250/250 250/250125/125 160/160 250/250 250/250125/125 125/125 200/200 200/200125/125 160/160 250/250 400/400
125(3)/125(3) 125(3)/125(3) 200(3)/200(3) 200(3)/200(3)
125(3)/125(3) 125(3)/125(3) 200(3)/200(3) 200(3)/200(3)
125(4)/125(4) 125(4)/125(4) 200(4)/200(4) 200(4)/200(4)
415 VAC AC-21 A / AC-21 BAC-22 A / AC-22 BAC-23 A / AC-23 B
690 VAC(2) AC-20 A / AC-20 BAC-21 A / AC-21 BAC-22 A / AC-22 BAC-23 A / AC-23 B
220 VDC DC-20 A / DC-20 BDC-21 A / DC-21 BDC-22 A / DC-22 BDC-23 A / DC-23 B
440 VDC DC-20 A / DC-20 BDC-21 A / DC-21 BDC-22 A / DC-22 BDC-23 A / DC-23 B
800/800 1000/1000
800/800 1000/1000
800/800 1000/1000
800/800 1000/1000
800/800 800/800800/800 800/800200/250 200/250800/800 1000/1000
800/800 1000/1000
800/800 1000/1000
800/800 1000/1000
800/800 1000/1000
800(4)/800(4) 1000(4)/1000(4)
800(4)/800(4) 1000(4)/1000(4)
800(4)/800(4) 1000(4)/1000(4)
630/630630/630500/500630/630500/500315/315160/200630/630630/630500/500500/500630/630
500(3)/500(3)
500(3)/500(3)
500(4)/500(4)
A. 32
�
Changeover switches
ATyS63 to 3200 A
The ATyS rangeATySATyS C30 / ATyS C40ATyS VISION softwareOther changeover switches
SOCOMEC general catalogue
ATyS — Characteristics (according to IEC 60947)
1800 A 2000 A 2500 A
Rated operational currents Ie (A)
Rated voltageAccording to IEC 60947-3
Load duty category A/B(1) A/B(1) A/B(1)
(1) A/B: Category with index A = frequent operation / Category with index B = infrequent operation. (2) With terminal shrouds or phase barrier. (3) 4-poledevice with 2 pole in series by polarity. (4) For a rated operating voltage Ue = 400 VAC. (5) Between the order given and the arrival in position (under the nomi-nal conditions). (6) Weight for ATyS 3e, 6e and 6m.
Thermal current Ith (40°C) Rated insulation voltage Ui (V) Rated impulse withstand voltage Uimp (kV)
Overload capacityRated short-time withstand current 1 s. Icw (kA rms) Rated peak withstand curent (kA peak)(4)
Connection
Maximum Cu cable section (mm2) Maximum Cu busbar width (mm)
Switching timeI — II or II — I (s)(5)
I — O or II — O (s)(5)
Power-supply toleranceSupply 230 VAC min / max (VAC)
Control supply power demandSupply 230 VAC inrush / nominal (VA)
Mechanical characteristicsEndurance (number of operating cycles)Weight of 3 p switch (ATyS 3) (kg) Weight of 4 p switch (ATyS 3) (kg)
A/B(1)A/B(1)
1000 1000 100012 12 12
1600 A100012
1250 A100012
3200 A100012
50 55 55110 120 120
50110
55120
Prospective short-circuit current (kA rms)(4) 100 — -100 -Associated fuse rated (A)(4) 1800 — -1600
35801001250 —
6 x 185 6 x 185 — -100 100 100 100
4 x 18563
Minimum Cu busbar section (mm2) 2 x 80 x 5 3 x 100 x 5 2 x 100 x 10 2 x 100 x 102 x 60 x 5 2 x 100 x 10-
100Tightening torque min / max (Nm) 40/45 40/45 40/45 40/4520/26 40/45
2.6 2.6 2 21.6 1.6 1 1
2.61.6
21
176/288176/288 176/288 176/288 176/288 176/288
450/120450/120 450/120 550/390 550/390 550/390
3 000 3 000 3 000 3 00036.142.1
36.142.1
47(6)
57(6)
51(6)
61(6)
4 00024.629.6
3 00059(6)
69(6)
A/B(1)
415 VAC AC-31 B 1800 2000 2500 320016001250
According to IEC 60947-6-1
Weight of 3 p switch (ATyS 6) (kg) 36.9 — 47(6) 51(6)25.4 59(6)
Weight of 4 p switch (ATyS 6) (kg) 42.9 — 57(6) 61(6)30.4 69(6)
Duration of “electrical blackout” I — II (s) 1.6 1.6 1 11.5 1
415 VAC AC-21 A / AC-21 BAC-22 A / AC-22 BAC-23 A / AC-23 B
690 VAC(2) AC-20 A / AC-20 BAC-21 A / AC-21 BAC-22 A / AC-22 BAC-23 A / AC-23 B
220 VDC DC-20 A / DC-20 BDC-21 A / DC-21 BDC-22 A / DC-22 BDC-23 A / DC-23 B
440 VDC DC-20 A / DC-20 BDC-21 A / DC-21 BDC-22 A / DC-22 BDC-23 A / DC-23 B
-/2500 -/3200-/2500 -/3200-/1600 -/1600
-/- -/—/- -/—/- -/—/- -/—/- -/—/- -/—/- -/—/- -/—/- -/—/- -/—/- -/—/- -/-
-/2000-/2000-/1600
-/—/—/—/—/—/—/—/—/—/—/—/-
1250/1250 1600/1600 1800/18001250/1250 1600/1600 1800/18001250/1250 1250/1250 1250/12501250/1250 1600/1600 1800/1800800/800 1000/1000 1000/1000800/800 1000/1000 1000/1000200/250 500/500 500/500
1250/1250 1600/1600 1800/18001250/1250 1250/1250 1250/12501250/1250 1250/1250 1250/12501250/1250 1250/1250 1250/12501250/1250 1600/1600 1800/1800
1250(3)/1250(3) 1250(3)/1250(3) 1250(3)/1250(3)
1250(3)/1250(3) 1250(3)/1250(3) 1250(3)/1250(3)
1250(3)/1250(3) 1250(3)/1250(3) 1250(3)/1250(3)
A. 33
Changeover switches
ATyS
SOCOMEC general catalogue
Dimensions• ATyS M 63 to 160 A • Cut out dimension
1
340
17610452
324
116
245
131,
5
45143
350
2613
73,553
46
186 x M6
atys
m_0
34_a
_1_x
_cat
324
47
atys
m_0
08_a
_1_c
at
10
W
U
MJ
J1
X T T T 11
C
H
Z2
Z1
10.5 Y Y
85
48
F
A
120
140
270
V
223
119
=
Fix.
180
Fix.
195
BA
CA
CA
AA
AC
101
=
Ø7
Ø9
Fix.
180
Fix.
195 1
32
3
3
4
5
6
CA
W
U
atys
_018
_e_1
_gb_
cat
1. Locking bracket with 3 padlocks max.
2. Maximum handle radius, operating angle 2 x 90°.
3. Connection and disconnection area.
4. Mounting spacers.
5. Terminal shrouds.
6. Handle.
1. Auxiliary contacts (2 max.).
C
244244
244.5244.5320.5
Rating(A)
Overall dimensions
Terminalshrouds Switch body
Switchmounting Connection terminals
A 3p. A 4p. AC F 3p. F 4p. H J 3p. J 4p. J1 M 3p. M 4p. T U V W X 3p. X 4p. Y Z1 Z2 AA BA CA
125 304 340 235 286.5 322.5 151 154 184 34 120 150 36 20 25 9 28 22 3.5 38 134 135 115 10160 304 340 235 286.5 322.5 151 154 184 34 120 150 36 20 25 9 28 22 3.5 38 134 135 115 10250 345 395 280 328 378 153 195 245 35 160 210 50 25 30 11 33 33 3.5 39.5 134.5 160 130 15400 345 395 280 328 378 153 195 245 35 160 210 50 35 35 11 33 33 3.5 39.5 134.5 170 140 15630 394 459 400 377 437 221 244 304 34 210 270 65 45 50 13 42.5 37.5 5 53 190 260 220 20
• ATyS 125 to 630 A
A. 34
�
Changeover switches
ATyS63 to 3200 A
The ATyS rangeATySATyS C30 / ATyS C40ATyS VISION softwareOther changeover switches
SOCOMEC general catalogue
Dimensions
M 51,5
53,5120120120
A
250
258
461
569
425
380
125
330
0
I
90°
504 Ø 4.5
Ø 31
50
atys
_678
_a_1
_x_c
at
Rating (A) Overall dimensions Switch mounting
A 3p. M 3p. M 4p.
2000 … 3200 596
A 4p.
716 347 467
• ATyS 2000 to 3200 A
F
12,5
=
207
169
166
280
250
166
V
=
250
AA
12,5
391,5
293
253,5
Z1
Y Y 48
94
X
M 51,5
J
T T T
1
3
BAC
23
34
5
6
U
atys
_019
_e_1
_x_c
at
1. Locking bracket with 3 padlocks max.
2. Maximum handle radius, operating angle 2 x 90°.
3. Connection and disconnection area.
4. Terminal screens.
5. Phase barrier shield.
6. Handle.
Rating(A)
Overalldimensions
Terminalshrouds Switch body Switch mounting Connection terminals
B AC F 3p. F 4p. J 3p. J 4p. M 3p. M 4p. T U V X Y Z1 AA
800 370 461 504 584 306.5 386.5 255 335 80 50 60.5 60 7 66.5 3211000 370 461 504 584 306.5 386.5 255 335 80 50 60.5 60 7 66.5 3211250 370 461 504 584 306.5 386.5 255 335 80 60 65 60 7 66.5 33016001800
380380
481481
596596
716716
398.5398.5
518.5518.5
347347
467467
120120
9090
4444
6666
88
67.567.5
288288
• ATyS 800 to 1800 A
A. 35
Changeover switches
ATyS
SOCOMEC general catalogue
Dimensions
33 8.58.5
50
3310
ø 9
ø 15
svr_
077_
a_1_
x_ca
t
16 x 11
60
28.5 15.7515.75
28.5
15
svr_
078_
b_1_
x_ca
t
15
5 5
12,5
25 253030
454590
ø12,5
svr_
098_
a_1_
x_ca
tConnection terminals
�
Cut out dimension
�
• ATyS 800 to 1000 A • ATyS 1250 A • ATyS 1600 to 3200 A
25274
37
74
37 60
129
155
30303030 132 30303030 22
210
30303030 148
225
acce
s_22
6_a_
1_ca
tac
ces_
232_
a_1_
cat
acce
s_23
3_a_
1_ca
t
acce
s_23
4_a_
1_ca
t
acce
s_22
9_a_
1_ca
t
acce
s_23
1_a_
1_ca
t
Copper bars connection kits�
• Fig. 1 • Fig. 2 • Fig. 3
atys
_649
_a_1
_x_c
at
atys
_650
_a_1
_x_c
at
50,5
20
138
101
50,5
20
138
165
ATyS 3s ATyS 3e, 6e, 6m
atys
_651
_a_1
_x_c
at
atys
_652
_a_1
_x_c
at
50,5
20
138
150
50,5
20
138
214
ATyS 3s ATyS 3e, 6e, 6m
• ATyS 125 to 630 A • ATyS 800 to 1800 A
A. 36
atys
_448
_b_1
_cat
Changeover switches
ATyS C30ATyS C40
SOCOMEC general catalogue
atys
_599
_b_1
_cat
FunctionsATyS C30 / C40 allows any type ofchangeover control: ATyS 3, SMV,contactors, circuit breakers or othermotorised switches.
Conformity tostandards• IEC 61010-1 • IEC 61000-4-8• IEC 61000-4-2 • IEC 61000-4-11• IEC 61000-4-3 • IEC 60068-2-6• IEC 61000-4-4 • IEC 60068-2-11• IEC 61000-4-5 • IEC 60068-2-30• IEC 61000-4-6
General characteristics• Modular design (6 modules)• DIN rail mounting• 2 outputs relays for changeover control.
ATyS C30• ATyS D10 or D20 possible connection• Inputs for auxiliary contacts position• Metering 3U on network 1• Metering 1U on network 2• 1 start/stop generator contact• Programmable inputs• Programmable outputs.
ATyS C40• Dual gensets controller with
a redundant genset application cycle• Single phase sensing on Gen1 & Gen 2• Programmable inputs• Programmable output• 2 start Gen contacts (Gen1 & Gen2).
�
The ATyS rangeATySATyS C30 / ATyS C40ATyS VISION softwareOther changeover switches
A. 37SOCOMEC general catalogue
21
3 4
ATyS 3s
ATyS C30 ATySD10/D20
atys
_149
_e_1
_x_c
at
Reference
Supplied from measurement circuitPower supply DC
1599 30301599 3031
Reference
-1599 3040
Supplied from measurement circuitPower supply DC
110 … 400 VAC< 9 … 30 VDC
Measurement range 110 … 400 VAC / ± 10%Fréquence 50 / 60 HzAccuracy ± 1%
13 14 23 24 33 34 43 44 53 54 301302303304305306 DC-DC+
205203106105104103
L3’L1’L1L2L3N
4 5
6 7 8 9 10
11 12
321
Characteristics
Applications
atys
_418
_b_1
_x_c
at
13 14 23 24 33 34 43 44 53 54 301302303304305306 DC-DC+
205203106104
L3’L1’L1L3
4 5
6 7 8 9 10
11 12
321
atys
_567
_a_1
_x_c
at
1. Generator 1 start / stop control2. Pos 1: control3. Pos 2: control4. O1 programmable output5. Generator 2 start / stop control6. CA1: auxiliary contact position1
7. I3 : programmable input8. CA2 : auxiliary contact position29. I1 : programmable input10. I2 : programmable input11. Metering 1U + frequency generator 112. Metering 1U + frequency generator 2
Terminals
1. Generator 1 start / stop control2. Pos 1: control3. Pos 2: control4. O1 programmable output5. O2 programmable output6. CA1: auxiliary contact position 17. CA0 : auxiliary contact position 0
8. CA2 : auxiliary contact position 29. I1 : programmable input10. I2 : programmable input11. 3 U network 1 and alimentation
measurement12. 1 U network 2 and alimentation
measurement
2
1 1í
3 3’
4
G1 G2
ATyS 3s
5
ATyS C40
1 & 1’. Generating sets measurment.2. Control and position information feedback.3 & 3’. Generating set “start/stop” control.4. External “start/stop” command for basic cycle.5. DC power supply.
atys
_566
_b_1
_x_c
at
Changeover switches
ATyS C30 / ATyS C40
References
atys
_448
_b_1
_cat
ATyS C30
atys
_599
_b_1
_cat
ATyS C40
ATyS C30 ATyS C40
1. Measurement and power supply.2. Control and position information feedback.3. Generating set “start/stop”.4. ATyS interface connection.
ATyS C30 ATyS C40
A. 38
couv
_128
_a_1
_cat
FunctionsATyS VISION is the monitoring and controlsoftware for ATyS 3e, 6e and 6m ranges. It operates in a Windows® 98, NT4 (pack 6),Millenium, 2000 or XP environment with aminimum PC configuration of: Pentium® II,64 Mb RAM, hard disk space of at least200 Mb, one or more RS232 or RS485serial ports, a 17” VGA 1024 x 768 screen.
General characteristicsThe ATyS VISION software allows you to visualise: • product status• all instantly measured electrical values• product configuration parameters• timer values• input and output status.
For each ATyS, you can export theconfiguration parameters to EXCEL.
ATyS VISION is available in a multilingualversion with the following languages:
• English• French• German• Italian
• Spanish• Chinese• Polish.
Versions and characteristics
ATyS VISION displays all the electricalvalues measured, configures the ATySparameters and allow remote testing.The user will also be able to importor export the configuration parameterswith EXCEL.
Changeover switches
ATyS VISIONsoftware
SOCOMEC general catalogue
485
232
SoftwareATyS VISION
PC
atys
_572
_a_1
_gb_
cat
bd_0
3_01
_01
�
The ATyS rangeATySATyS C30 / ATyS C40ATyS VISION softwareOther changeover switches
Find on the SOCOMEC Web Site www.socomec.com
A. 39
Changeover switches
ATyS VISION software
SpecificationSettings:• communication parameters• automatic recognition product.
Display:• ATyS software version• serial number• connected input/output modules• input/output status • product status• test status.
Configuration:• product configuration• network type • voltage and frequency thresholds • timers• inputs/outputs• Excel import or export capability.
Measurement:• normal and backup sources voltage and frequency measurment• current measurment I1, I2, I3 In (measurment ATyS 6m only) • power P, Q, S per phase and total (measurment ATyS 6m only)• power factor per phase (measurment ATyS 6m only)• timer values and countdown• source status, switch position.
Test:• on load (with load transfer) • off load (remote starting and stopping of generating set) • product monitoring in position I, 0 or II.
SOCOMEC general catalogue
atys
_608
_a_1
_x_c
at
ATyS status.
atys
_609
_a_1
_x_c
at
ATyS configuration.
atys
_611
_a_1
_x_c
atat
ys_6
10_a
_1_x
_cat
Measurement.
Remote testing & control.
Find on the SOCOMEC Web Site www.socomec.com
bd_0
3_03
_01
A. 40
bd_0
3_04
_01
Conformity to standards• IEC 60947-3• BS EN 60947-3• EN 60947-3• NBN EN 60947-3• VDE 0660 Part 107 (1992)
Changeover switches
Other changeoverswitches
SOCOMEC general catalogue
SOCOMEC provides a wide range ofstandard or adapted manual andmotorised changeover & by-passswitches.Do not hesitate to consult us.
SIRCO VM1FunctionsThey are manually operated three or fourpole switches.They provide switching, source inversionand changeover under load of two lowvoltage power circuits, as well as theirsafety isolation.
General characteristics• 63 to 125A ratings, 3 and 4 pole• 3 stable positions (I, 0, II or I, I+II, II) and
facility to switch from one to the otherunder load (AC22 and AC23)
• Fully visible breaking• Double visible breaking.
com
mut
_004
_a_1
_cat
SIRCOVER by-pass
svr_
119_
a_1_
cat
FunctionsSIRCOVER by-pass products are manuallyoperated changeover switches. They are a combination of threeinterlocked switches enabling the use with 3+6 poles or 4-8 poles.They insulate by providing simultaneoussafety loads or low voltage circuits mainlyduring maintenance operation.
General characteristics• 125 to 1600A, 3+6 or 4+8 poles• 3 stable positions (I, 0, II or I, I+II, II)• High electrical performance (AC23)• Fully visible breaking.
SIRCOVER
svr_
099_
a_2_
cat
FunctionsSIRCOVER products are manuallyoperated multipolar switches.They ensure switching, transfer of sourcesor transfer of two low voltage circuits aswell as their safety disconnection.
General characteristics• 125 to 3200A, 3 and 4 pole• 3 stable positions (I, 0, II or I, I+II, II)• High electrical characteristics (AC23)• Fully visible breaking.
�
The ATyS rangeATySATyS C30 / ATyS C40ATyS VISION softwareOther changeover switches
A. 41
Changeover switches
Other changeover switches
ATS by-pass switches
svr_
134_
a_1_
x_ca
t
FunctionsThey are used to isolate a changeoverswitching device and changeover the loadto an emergency supply.
SOCOMEC general catalogue
General characteristics• 125 and 1600 A, 4 pole only• 3 stable positions.
Enclosed manual changeover switches
coff_
298_
a_2_
cat
FunctionsEnclosures equipped with manualchangeover switches provide emergencybreaking and changeover switching, formaintenance or safety isloation in thevicinity of any low voltage final circuit.
Motorised mixed pole changeover switches
atys
_725
_a_1
_cat
FunctionsThey provide switching and sourceinversion for low voltage sources of different power ratings.
General characteristics• Steel or polyester enclosure• From 63 to 1600A, 4 pole• Fully visible breaking• Double door locking• Triple locking of the handle.
General characteristics • 1250 to 3200A ratings, 3 and 4 pole.
A. 42 SOCOMEC general catalogue
Notes
A. 43SOCOMEC general catalogue
VALID FOR FRANCE
H E A D O F F I C ESOCOMEC GROUPS.A. SOCOMEC capital 11 065 700 €
R.C.S. Strasbourg B 548 500 149B.P. 60010 — 1, rue de Westhouse — F-67235 Benfeld Cedex — FRANCE
I N T E R N A T I O N A L S A L E S D E P A R T M E N TSOCOMEC1, rue de Westhouse — B.P. 60010F — 67235 Benfeld Cedex — FRANCETel. +33 (0)3 88 57 41 41 — Fax +33 (0)3 88 74 08 [email protected]
Socomec worldwide
I N E U R O P E
BELGIUMSOCOMEC BELGIUM SAB — 1190 BruxellesTel. +32 (0)2 340 02 30 — Fax +32 (0)2 346 28 [email protected]
FRANCESOCOMECF — 67235 Benfeld Cedex Tel. +33 (0)3 88 57 41 41 — Fax +33 (0)3 88 74 08 [email protected]
GERMANYSOCOMEC Schaltgeräte GmbHD — 35510 ButzbachTel. +49 (0) 6033 98 07 0 — Fax +49 (0) 6033 98 07 [email protected]
ITALYSOCOMEC Elettrotecnica SpaI — 20098 S. Giuliano Milanese (MI)Tel. +39 02 98 498 21 — Fax +39 02 98 243 [email protected]
SPAINSOCOMEC ELECTRO, S.L.E — 08310 Argentona (Barcelona) Tel. +34 93 741 60 67 — Fax. +34 93 757 49 [email protected]
THE NETHERLANDSSOCOMEC B.V.NL — 3992DE HoutenTel. +31 (0)30 63 71 504 — Fax +31 (0)30 63 72 [email protected]
I N T H E U N I T E D K I N G D O M
SOCOMEC LtdUK — Knowl Piece — Wilbury WayHitchin Hertfordshire SG4 0TY Tel. 01462 440033 — Fax 01462 [email protected]
I N A S I A
CHINASOCOMEC CHINACN — 20030 P.R.C ShanghaiTel. +86 21 5298 9555 — Fax +86 21 6228 [email protected]
SOUTH EAST ASIASOCOMEC THAILANDTH — BangkokTel. +66 2 982 80 51 — Fax +66 2 982 80 [email protected]
I N M I D D L E E A S T
UNITED ARAB EMIRATES SOCOMEC Middle EastDubai, U.A.E.Tel. +971 4 88 11 623 — Fax +971 4 88 19 [email protected]
www.socomec.comThis document is not a contract. SOCOMEC reserves the right to modify features without prior notice in view of continued improvement.