[Page 1] SystemAir EC Vent EC Vent User Manual -EN_GB 15-03-2011V.A-003 |
[Page 2] SystemAir EC Vent Contents 1 Warnings ………………………………………………………………………………………………………………….. 1 2 Product Description ………………………………………………………………….. |
[Page 3] SystemAir EC Vent 1Warnings The following admonitions will be presented in the different sections of the document. Danger • Make sure that the Mains supply to the unit is disconnected before performing any maintenance or electrical work! • All electrical connectio… |
[Page 4] SystemAir EC Vent Fig. 1 Room unit components Position Description Explanation 1Display Shows symbols, menus and settings 2 Selection knob Move through the menu lists or change settings and values by turnin g the knob left or right 3 Confirm button Confirm menu choi… |
[Page 5] SystemAir EC Vent 2.1.1 Display Symbols Symbol Description Explanation Fan speed Illustrates the current set fan speed. The speed setting is stepless or in steps determined by the user. The speed is also displayed as percentage of the maximum fan speed at the bottom o… |
[Page 6] SystemAir EC Vent 3Operation 3.1 Before starting Before sta rt ing up the system m ake sure you have checked the following: • That the equipment is installed according to the installation instructions • That the correct accessories are used for the intended functi… |
[Page 7] SystemAir EC Vent • Extended time: 00:30 (remaining time counter, in this example the remaining extended time is 30 minutes) •Away • Manual: (If the controller is set to stepless the fan signal output is shown in %. If step controller is selected the selected st… |
[Page 8] SystemAir EC Vent 3.2.3 U ser Overview Auto Monday 12:00 Auto Password Service Setup xxxx Password xxxx 12:00 20°C Auto Fan Speed <500RPM A B C D E F G Fig. 2 User overview EC Vent User Manual 6 System air AB |
[Page 9] SystemAir EC Vent Table 1: Explanations User overview Position Description (figure 2) A Shows a warning symbol with the text Fan speed <500 rpm. Indicates that no fan speed setting has been made B Sleep mode display option. Will b e shown after 5 min. of inactivit… |
[Page 10] SystemAir EC Vent 3.2.4 User Menu Auto Mode Auto Fan Speed <500RPM Setting Password Service xxxx Away Auto Extended time Boost Manual Away Auto Extended time Boost Manual Away Auto Extended tim… |
[Page 11] SystemAir EC Vent Table 2: Explanations User menu Auto mode Position Menu Headline Description (fi gu re 3) A Away Activate the Away function. For more info. (section 3.2.2.2 and section 3.2.7). B Auto Abort away, boost or extended time. The fan will then be controll… |
[Page 12] SystemAir EC Vent 3.2.5 Service Menu Service • Fan set point adjustment • Heater / Cooler set point • Time and Date Fan set point xxx °C / ppm / %Rh / Pa / l/s Service • Fan set point adjustment • H eater / Cooler set point • Time and Date Time and d… |
[Page 13] SystemAir EC Vent Explanations cont’d Position Menu Headline Description (fi gu re 4) E Time and Date Change the t i me and date F SW Version Software versio n EC Vent User Manual 11 System air AB |
[Page 14] SystemAir EC Vent 3.2.6 Installation 3.2.6.1 Installation-1 Control mode • Disable • Temperature Control • CO 2 Control • Humidity Control • Pressure Control • Flow Control • Slave Control Installation • Contro… |
[Page 15] SystemAir EC Vent Table 4: Explanations installation-1 Position Menu Headline Description (fi gu re 5) A Installation Installation, main m enu options B Controllers Control 1-5 gives you the possibility to run thefanwiththehelpof5differentsensors, either simultaneous… |
[Page 16] SystemAir EC Vent 3.2.6.2 Installation-2 Installation • Controllers • User interface • Security • Output • Alarm Setting • Address • Adjusting • Units Installation • Controllers • User interface • Security • Output • Alarm Setting • Address… |
[Page 17] SystemAir EC Vent Table 5: Explanations installation-2 Position Menu headline Description (fi gu re 6) A Alarm setting Output – Possibility to set an output signal (Digital/Analogue) e.g. Alarm output if fan speed is to low or analogue (0-10V) signal to another fan… |
[Page 18] SystemAir EC Vent 3.2.7 U ser Interface User interface • Sleep mode • Boost time • Extended time • Away • Language Sleep mode Sleep mode enable / disable Background Logo / Clock / Temp Extended time Disable / 00:01 -23:59 Boost time… |
[Page 19] SystemAir EC Vent Table 6: Explanations User interface Position Menu headline Description figure 7) A Sleep mode Choose if sleep mode should be enabled or disabled. If enabled, choose what should be displayed when the room unit goes in to sleep mode (5 min.)(section … |
[Page 20] SystemAir EC Vent 3.2.8 Alarm Menu N Alarm Alarm 1 fan speed <500 RPM Mon 12:00 Alarm active / not active Reset / Block A B C D E F Fig. 8 Alarm Menu Position Description A Indicates number of active alarms B Shows the reason for the alarm C Shows weekday and time… |
[Page 21] SystemAir EC Vent 3.2.9 Temperature Control Temperature Control • Sensor • Control Function • Min/max speed • PI setting • Set point Sensor Board: CB/RU 1/RU 2. . Channel : 1/2/3/Int Control function Higher speed at higher temperature / Lower speed at hig… |
[Page 22] SystemAir EC Vent Table 7: Explanations Temperature control Position Menu headline Description (fi gu re 9) A Sensor Set where the temperature sensor is being connected or if the internal sensor is being used. If an external sensor is being used there are 5 different… |
[Page 23] SystemAir EC Vent 3.2.10 CO 2 Control CO 2 Control • Sensor • Sensor range • Min/max speed • PI setting • Set point Min/max speed Max 15-100 % Min Off / 15-100 % CO 2 Control • Sensor • Sensor range • Min/max speed • PI setting • Set point Sensor… |
[Page 24] SystemAir EC Vent Table 8: Explanations CO 2 control Position Menu headline Description (figure 10) A Sensor Set where the CO 2 sensor is being connected; there are 5 different analogue inputs to choose from, 2 on the room unit and 3 on the control board. If a CO 2 s… |
[Page 25] SystemAir EC Vent 3.2.11 Humidity Control Humidity Control • Sensor • Sensor range • Min/max speed • PI setting • Set point Humidity Control • Sensor • Min/max speed • PI setting • Set point Sensor range Min xxx %Rh Max xxx %Rh Humidity Control • S… |
[Page 26] SystemAir EC Vent Table 9: Explanations humidity control Position Menu headline Description (figure 11) A Sensor Set w here the humidity sensor is being connected or if the internal sensor is being used. If an external sensor is being used there are 5 different analo… |
[Page 27] SystemAir EC Vent Table 10: Explanations Manual control Position Menu headline Description (figure 12) A Mode Activate the manual contro l mode B Step/Stepless/Disable Choose if you want the fan to be controlled manually (3 to 5 steps) or stepless. The user can then … |
[Page 28] SystemAir EC Vent 3.2.13 Time Control Schedule Schedule 1-14 Clear Y/N On HH:MM DDD Off HH:MM DDD Fixed Speed / set point xxxx°C / ppm / %Rh / % A D F B C E Fig. 13 Time Control Table 11: Time control Position Menu headline Description (figure 13) A Schedule Up to … |
[Page 29] SystemAir EC Vent 3.2.14 Pressure Control Pressure Control • Sensor • Sensor range • Min/max speed • PI setting • Set point • Set point displacement Pressure Control • Sensor • Sensor range • Min/max speed • PI setting • Set point • Set point d… |
[Page 30] SystemAir EC Vent Table 12: Explanations Pressure control Position Menu headline Description (figure 14) A Sensor Set where the pressure sensor is being connected; there are 5 different analogue inputs to choose from, 2 on the room unit and 3 on the control board. B … |
[Page 31] SystemAir EC Vent 3.2.15 DI Control Function Go to fixed speed /Change set point /auto mode New setpoint / speed xxx °C / ppm / %Rh / l/s / or Off / 15-100 % DI control X • Input • Function • NO/NC • Delay • Enable DI control X • Input • Function �… |
[Page 32] SystemAir EC Vent Explanations DI control cont’d Position Menu headline Description (figure 15) G Delay → Delay Choose if you want the desired action (PositionE)tobedelayedfromthetime that the DI in being activated. 00:00:00 means that the required action will… |
[Page 33] SystemAir EC Vent 3.2.16 Flow Control Flow Control • Sensor • Sensor range • Min/max speed • PI setting • Set point • Set point displacement Flow Control • Sensor • Min/max speed • PI setting • Set point • Set point displacement Sensor range Max … |
[Page 34] SystemAir EC Vent Table 14: Explanations Flow control Position Menu headline Description (figure 16) A Sensor Set where the flow sensor is being connected; there are 5 different analogue inputs to choose from, 2 on the room unit and 3 on the control board. B Sensor … |
[Page 35] SystemAir EC Vent 3.2.17 Slave Control Slave Control • Input • Min / Max speed Slave Control • Input • Min / Max speed Min/max speed Max 15-100 % Min Off / 15-100 % Sensor Board: CB/RU 1/RU 2. . Channel : 1/2/3 A B Fig. 17 Slave control Table 15: Explanations… |
[Page 36] SystemAir EC Vent 3.2.18 Heater/Cooler Control 3.2.18.1 Heater/Cooler Control part 1 Temperature Control • Sensor • Output • Control Function • PI setting • Set point • Min/max temperature sensor • Min/Max temperature • Min flow shut off • Enable �… |
[Page 37] SystemAir EC Vent Table 16: Explanations Temperature control Position Menu headline Description (figure 18) A Sensor Set where the temperature sensor that will be the controlling sensor is being connected. There are 5 different analogue inputs to choose from, 2 on th… |
[Page 38] SystemAir EC Vent 3.2.18.2 Heater/Cooler Control part 2 Temperature Control • Sensor • Output • Control Function • PI setting • Set point • Min/max temperature sensor • Min/Max temperature • Min speed shut off • Enable Min/Max temperature Min No… |
[Page 39] SystemAir EC Vent 3.2.19 Output Output • Out 1 • Out 2 • Out 3 Out 1 • Type • Event • Enable Out 1 • Type • Event • Enable Type 0-10V/DO Follow Fan speed Offset +- 0-100 % Fan speed threshold On if Over/Under 10-100 % Out 2… |
[Page 40] SystemAir EC Vent Explanations Output cont’d Position Menu headline Description (figure 20) D Enable Set if the output function for this specific output is enabled or disabled. E Fan speed threshold If digital signal is c hosen under position A; Chose at what f… |
[Page 41] SystemAir EC Vent Table 19: Explanations Alarm Position Menu headline Description (figure 21) A Fan speed Set at what fan speed (rpm) the fan speed alarm should be triggered. B Analogue input Set the alarm limits for the different sensors that have been installed. C … |
[Page 42] SystemAir EC Vent 2 Ser vice icon Select the service icon in the main menu screen. 3Setup Select Set up to enter into the Installation menu. 4 Controllers Select Controllers. 5 Control 1 Select Control 1. 6 Pressure Go down to and select Pressure. 7 Sensor Select CB (… |
[Page 43] SystemAir EC Vent 13 Set point displacement/Setting Set b et we en which tempera tures yo u want the pressure displaceme nt . Set Start fo r examp le to 0,0 °C and Stop to -10 °C. Set the Displacement to -50 Pa. Note: This is only possible if the value in the set po… |
[Page 44] SystemAir EC Vent 6 Function Select Function 7Off Select Fixed speed and choose New speed off % 8NO/NC Go to NO/NC and Select Closed Note: The switch needs to be closed in order for this to function. (see “Explanations DI control” (table 13) for more info. Press t… |
[Page 45] SystemAir EC Vent 1 Install air speed sensor and CO 2 sensor Install the air speed sensor in the ventilation duct and the CO 2 sensor in the ventilated area. Connect the air speed sensor to the control board to IN 1 (pos. B) and the CO 2 sensor to RU 1 (I1) on the roo… |
[Page 46] SystemAir EC Vent 8 Sensor rang e Select Sensor range and set the maximum airflow for the air speed sensor in l/s. Note: The range of the analogue air speed sensor is normally given in m/s written on the sensor label. You have to c alculate the l/s depending on the a… |
[Page 47] SystemAir EC Vent 16 Min/Max speed Set Min and Max speed. For example Min 15% and Max 100%. Step back to the previous frame with the back button. 17 PI setting Set P-band and I-time. Set P-band 200 ppm,andI-time to Off since the sens or set point will be fixed. Step … |
[Page 48] SystemAir EC Vent 7 Sensor rang e Set t he sens or ran ge to Min 10% and Max 90% Step back to the previous frame with the back button. 8 Min /Max sp eed Set Min and Max speed. For example Min 15% and Max 100%. Step back to the previous frame with the back button. 9 Se… |
[Page 49] SystemAir EC Vent 4Setting Go to Setting and set min. and max speed to for example Min 40% and Max 40%. The user will now only be able to set the manual speed of the fan to 40%. 5 Controllers Go back to Controllers,selectDI Control andgoontoselectingDI1.Confirm Step … |
[Page 50] SystemAir EC Vent 1 Install the temperature sensor Install the tempe r ature sensor used for the control of the radiator in the ventilated space and connect it to the control board on IN 1 (pos. B). 2 Temperature control cooling Start with the control function, which … |
[Page 51] SystemAir EC Vent 9 Heating control Go to Heater/Cooler and select Sensor. 10 Sensor Choose CB I1. Step back to the previous frame with the back button. 11 Output Go to Output and select Control Board AO1. Step back to the previous frame with the back button. 12 Contr… |
[Page 52] SystemAir EC Vent Table 20: Operation schedule examples Example Description On 07:00 Mon Off 16:00 Mon Speed 50 % The system runs at 50% speed 07:00 on Monday and stays like that until 16:00 the same day. If nothing else is set in the rest of the 13 possible schedules… |
[Page 53] SystemAir EC Vent 3.4.1 S et up example we will use the set up case based on above example “Pressure control with outdoor temperature compensa tion” (section 3. 3. 1). In this imagined example you want the week program to achieve the following result: • Monday t… |
[Page 54] SystemAir EC Vent The Time control function check box is filled whenever there is an active schedule. It is disabled by erasing all settings in each programmed schedule or if there is no active schedule at the time. Erasing the schedules is easiest done by selecting … |
[Page 55] SystemAir EC Vent EC Vent User Manual 53 System air AB |
[Page 56] SystemAir EC Vent lastpage Systemair AB reserves the right to make changes and improvements to the contents of this manual without prior notice. Systemair AB Industrivä gen 3 SE-739 30 Skinnskatteberg, Sweden Phone +46 222 440 00 Fax + 46 222 440 99 www.system air.co… |
Systemair
K EC, KVO EC, KVKE EC. Вентиляторы для круглых каналов. Инструкция по эксплуатации и техническому обслуживанию.
Скачать
Pdf 2.18 Mb
Язык: RU, EN, DE, IT, FR, NL
Document’s Content and Additional Information | Share Manual |
---|---|
SystemAir EC Vent Operation & user’s manual
Pages Preview: Document Transcription:
See Details |
Systemair EC-VENT ROOM UNIT
Systemair EC-VENT ROOM UNIT, артикул 3018, это не просто регулятор для ЕС вентиляторов. Это устройство, которое совместно с ЕС вентиляторами упрощает осуществление вентиляции по потребности, делая установку и управление более простым.
Уникальность Systemair EC-VENT ROOM UNIT это возможность иметь различные функции управления и возможность подключения до 5 датчиков (аналоговых или дискретных). Один параметр такой, как температура может контролироваться в нескольких различных местах. Альтернативно, несколько параметров (СО2, влажность, температураи т.д.) могут быть объединены для управления вентилятором напрямую или как дополнение к недельному таймеру и/или ручное управление для увеличения объема вентиляции, если требуется. Также может использоваться, как регулятор нагревателя или дополнительного вентилятора по сигналу 0-10В.
Systemair EC-VENT ROOM UNIT состоит из двух блоков, один центральный блок управления находится непосредственно возле вентилятора, а второй блок- пульт управления с дисплеем обычно размещается в обслуживаемом помещении, в месте со свободным доступом для пользователя. Блок управления и пульт управления соединяются сигнальным кабелем. EC-Vent предлагает подключать до 5 датчиков, которые постепенно определяют фактическую потребность вентиляции, тем самым EС вентиляторы управляются плавно для достижение точной потребности в вентиляции, которая требуется в данный момент времени. Как результат, хороший микроклимат в помещении и низкие счета за электричество.
— Блок управления и пульт управления пригодны для использования различных датчиков, например датчиков температуры, влажности и CO2.
— Комнатный пульт управления имеет встроенные датчики: СО2 и температуры.
— Возможность программировать недельный таймер.
— Встроенный трансформатор 24В для питания датчиков, заслонок и т.д.
— Дружественное меню.
— Используетя для EC-Vent CB
— Допустимый диапазон температуры окружающей среды — 0…50°C
— Класс защиты корпуса — 20IP
— Вес — 0.3кг